5704.2.7.5 Tank openings other than vents.
Tank openings for other than vents shall comply with the requirements of FC 5704.2.7.5.1 through 5704.2.7.5.8.
5704.2.7.5.2 Filling, emptying and vapor recovery connections.
Filling, emptying and vapor recovery connections to tanks shall be located outdoors at a location free from sources of ignition and not less than 10 feet (3048 mm) away from building openings. Such openings shall be provided with a liquid-tight cap which shall be closed when not in use and properly identified.
5704.2.7.5.3 Piping, connections and fittings.
Piping, connections, fittings and other appurtenances shall be installed in accordance with FC 5703.6.
5704.2.7.5.4 Manual gauging.
Openings for manual gauging, if independent of the fill pipe, shall be provided with a liquid-tight cap or cover. Covers shall be kept closed when not gauging. Openings for manual gauging shall not be allowed for tanks installed indoors.