Loading...
5704.4.7 Weather protection.
Weather protection for outdoor portable container storage areas shall be in accordance with FC 5004.13.
5704.4.8 Empty containers storage.
The storage of empty containers previously used for the storage of flammable or combustible liquids shall be stored as required for filled containers. Containers when emptied shall have the covers or plugs immediately replaced in openings.
5705.1 Scope.
The handling and use of flammable and combustible liquids, including the dispensing and mixing of such liquids, shall be conducted in accordance with this chapter. Cargo tank and tank car loading and unloading and other special operations shall be conducted in accordance with FC 5706.
Exception: Containers of organic coatings having no fire point and which are opened for pigmentation are not required to comply with the requirements of this section.
5705.2 Liquid transfer.
Liquid transfer equipment and methods for transfer of Class I, II and IIIA liquids shall be subject to the approval of the commissioner and conducted in compliance with the requirements of FC 5705.2.1 through 5705.2.7.
5705.2.1 Pumps.
Positive-displacement pumps shall be provided with pressure relief discharging back to the tank, pump suction or other approved location, or shall be provided with interlocks to prevent over-pressure.
Loading...