5704.3.3.2 Incompatible materials.
Materials that will react with water or other liquids to produce a hazard shall not be stored in the same room with flammable and combustible liquids in accordance with FC 5003.9.8.
5704.3.3.3 Clear means of egress.
Storage of any liquids, including stock for sale, shall not be stored near or be allowed to obstruct physically the route of egress.
5704.3.3.4 Empty containers storage.
The storage of empty containers previously used for the storage of flammable or combustible liquids shall be stored as required for filled containers. Containers, when emptied, shall have the covers or plugs immediately replaced in openings, be removed to an outdoor location and, if not cleaned on the premises, the empty containers shall be removed from the premises as soon as practical, but at least daily.
5704.3.3.5 Shelf storage.
Shelving shall be of approved noncombustible construction, adequately braced and anchored. Seismic requirements shall be in accordance with the construction codes, including the Building Code.
5704.3.3.5.1 Reserved.
5704.3.3.5.2 Displacement protection.
Shelves shall be of sufficient depth and provided with a lip or guard to prevent individual containers from being displaced.
Exception: Shelves in storage cabinets or on laboratory furniture specifically designed for such use.
5704.3.3.5.3 Orderly storage.
Shelf storage of flammable and combustible liquids shall be maintained in an orderly manner.
5704.3.3.6 Rack storage.
Where storage on racks is allowed elsewhere in this code, a minimum 4-foot-wide (1219 mm) aisle shall be provided between adjacent rack sections and any adjacent storage of liquids. Main aisles shall have a minimum of 8 feet (2438 mm).