5704.2.7.10 Leak reporting.
A consistent or accidental loss of liquid, or other indication of a leak from a tank system, shall be reported immediately to the department and other authorities having jurisdiction.
5704.2.7.10.1 Leaking tank disposition.
Leaking tanks shall be promptly emptied, repaired and returned to service, sealed in place or removed in accordance with FC 5704.2.13.
5704.2.7.11 Tank lining.
Steel tanks are allowed to be lined only for the purpose of protecting the interior from corrosion or providing compatibility with a material to be stored. Only those liquids tested for compatibility with the lining material are allowed to be stored in lined tanks. Tank lining shall not be used for purposes of repairing a tank.
5704.2.8 Reserved.
5704.2.9 Aboveground tanks.
Aboveground storage of combustible liquids in tanks shall comply with the requirements of FC 5704.2, and FC 5704.2.9.1.2 through 5704.2.9.6.9. Except as specifically authorized in FC 5706, the storage of flammable liquid in aboveground storage tanks is prohibited.