908.1 General.
Emergency alarm systems required by the construction codes, this code or the rules for the detection and notification of a release of a hazardous material or other hazardous materials incident, or other physical or health hazard, including systems designed to detect flammable, toxic, asphyxiant and other gases, shall be designed, installed, operated and maintained in compliance with the construction codes, the Electrical Code, the code requirements referenced in FC Table 908.1, this section and the manufacturer's instructions.
Hazard | Occupancy / Use a | Section |
Hazard | Occupancy / Use a | Section |
Carbon dioxide | Occupancies with a carbon dioxide beverage dispensing system | |
Carbon monoxide | Residential occupancies; other occupancies with carbon monoxide-producing equipment | Building Code BC 915 |
Flammable alcohol vapors | Distilleries | |
Gaseous hydrogen | Hydrogen fuel gas rooms | |
Hazardous materials | High-hazard occupancies (Group H) | |
Hazardous production materials | Semiconductor production facilities (Group H-5) | |
Lighter-than-air motor fuels | Motor fuel-dispensing facilities; repair garages for vehicles fueled by lighter-than-air motor fuels | |
Medical gases | Hospitals, nursing homes and hyperbaric facilities with a medical gas system | |
Natural gas and other flammable gases (except lighter-than-air motor fuels) | Mechanical rooms, microturbine rooms and power plants with flammable gas distribution piping operating above 15 psig; residential occupancies | |
Ozone gas | Ozone gas-generator rooms | |
Refrigerants | Mechanical rooms with a refrigerating system | |
Toxic/highly toxic materials | Group H-3 occupancies | |
a. Typical occupancy/use. Other occupancies/uses as approved.
908.2 Plan approval.
Design and installation documents for emergency alarm systems shall be submitted for department review and approval when required by FC 105.4 and the rules.
908.3 Signage.
Signs shall be posted in a conspicuous location near the emergency alarm system control panel and each alarm notification device to inform building occupants in the affected area of the meaning of the alarm activation and the appropriate response.
908.4 Central station monitoring.
Emergency alarm systems required to transmit an alarm signal to a central station shall transmit such signal through the central station-monitored fire alarm system for the building or occupancy, or through an approved central station-monitored control panel. Such central station connections shall be maintained in compliance with the requirements of NFPA 72, as modified by FC Appendix B, and the rules.