314.5 Required clearance from fire safety systems.
Sprinklers and fire alarm systems shall not be obstructed by indoor displays.
314.5.1 Sprinkler systems.
A sprinkler system shall be installed in or under covered kiosks, displays, booths, or concession stands that exceed 4 feet (1219 mm) in width. The clearance between any sprinkler head deflector installed above the top of the kiosks, displays, booths, or concession stands shall not be less than 18 inches (457 mm).
Exception: Open-grid and drop-out ceilings complying with the requirements of NFPA 13, as modified by FC Appendix B, may be installed beneath sprinklers.
314.5.2 Fire alarm systems.
Sufficient clearance shall be provided between kiosks, displays, booths, or concession stands and fire alarm and carbon monoxide systems equipment and devices including detectors and strobes, so as not to interfere with their operation.
315.1 General.
Storage of materials shall be in accordance with this section.
Exception: Storage of materials during construction and demolition operations shall comply with the requirements of FC Chapter 33.
315.2 Storage in buildings.
Storage of materials in buildings shall be orderly and stacked materials shall be stable. Storage of combustible materials shall be separated from heaters or heating devices by distance or shielding so that ignition cannot occur.
315.2.1 Ceiling clearance.
Storage shall be maintained 2 feet (610 mm) or more below the ceiling in areas of buildings not protected by a sprinkler system, or a minimum of 18 inches (457 mm) below sprinkler head deflectors in areas protected by a sprinkler system, provided, however, that storage of noncombustible materials to the ceiling may be authorized by the department when such storage is within 30 inches (762 mm) of a fire partition.