315.3 Outdoor storage.
Outdoor storage of combustible materials in quantities in excess of 32 cubic feet (0.91 m
3) shall comply with FC 315.3.1 through 315.3.6.
315.3.1 Property line.
Except as otherwise provided in FC 315.3.5, outdoor storage of combustible materials shall not be located within 10 feet (3048 mm) of a property line.
315.3.2 Adjoining properties.
Except as otherwise provided in FC 315.3.5, outdoor storage of combustible materials shall not be located within 50 feet (15 240 mm) of the nearest wall of a building occupied as a Group A occupancy, Group E educational occupancy, Group I-2 occupancy, or any building, structure or premises used for a public gathering.