Loading...
(a) Quantities exceeding five hundred (500) cubic feet of loose combustible fiber shall be stored in fire-resistive storage rooms conforming to the applicable provisions of Section 3129.43(c), having incombustible floor, wall and ceiling construction with a fire resistance rating of not less than two (2) hours. However, when the quantity of combustible fiber stored in such rooms exceeds one thousand (1,000) cubic feet, the required fire resistance rating shall be not less than four (4) hours for walls and partitions and not less than three (3) hours for floor and ceiling construction.
(b) All such fire-resistive rooms shall have provisions for venting gas and smoke to the outer air as specified in Section 3129.43(c), except that the required vent area need not exceed one (1) square foot for each two hundred (200) cubic feet of room volume.
(c) All interior openings within enclosures of such fire-resistive storage rooms shall have self-closing or automatic opening protectives. Enclosures required to have a fire resistance rating of two (2) hours shall have opening protectives with a fire resistance rating of not less than one and one-half (1-1/2) hours. Enclosures required to have a fire resistance rating greater than two (2) hours shall have openings protected with opening protectives on both sides of the opening. Such opening protectives shall have a combined fire resistance rating of not less than four (4) hours.
(Ord. No. 991-49. Passed 6-27-49, eff. 6-27-49)
Isolated storage buildings for the storage of loose combustible fiber shall be not less than fifty (50) feet from other buildings not on the same property and not less than fifty (50) feet from lines on adjacent property where buildings may be built. Such isolated storage buildings shall be not less than twenty (20) feet from buildings on the same property and shall in all cases be suitably located where approved by the Fire Chief, with openings properly protected against the entrance of sparks. The maximum quantity of loose combustible fiber stored in one (1) isolated storage building shall be two thousand five hundred (2,500) cubic feet.
(Ord. No. 991-49. Passed 6-27-49, eff. 6-27-49)
Loose combustible fiber not in suitable bales or packages shall not be stored in the open within one hundred (100) feet of any building or any line on adjacent premises on which buildings may be built. Combustible fiber in bales or packages stored outdoors shall conform to Section 385.76.
(Ord. No. 991-49. Passed 6-27-49, eff. 6-27-49)
(a) Storage warehouses and rooms for baled combustible fiber shall be classified as high hazard occupancy and all such warehouses and rooms shall be of Class I-A, fireproof construction.
(b) No piles of baled combustible fiber in such storage warehouse or room shall exceed nine (9) feet in height and no single storage compartment shall exceed five thousand (5,000) square feet in floor area.
(c) Floors shall be designed to support safely the water-saturated weight of the combustible fiber to be stored thereon.
(d) All interior walls of storage rooms shall have fire resistance ratings of not less than four (4) hours and all openings in such walls shall have opening protectives installed on both sides of the opening. Such opening protectives shall have a combined fire resistance rating of not less than four (4) hours.
(Ord. No. 991-49. Passed 6-27-49, eff. 6-27-49)
(a) Blocks or piles of baled fiber stored in storage warehouses or rooms shall be separated from adjacent storage by aisles not less than five (5) feet wide; or by flash fire barriers consisting of continuous sheets of incombustible material extending from the floor to a height of at least one (1) foot above the highest point of the piles and projecting at least one (1) foot beyond the sides of the piles.
(b) Sisal and other fibers in bales bound with combustible tie ropes, and jute and other fibers liable to swell when wet, shall be stored to allow for expansion in any direction to the extent of twenty percent (20%) of their bulk without endangering building walls, ceilings or columns. Not less than three (3) feet clearance shall be maintained between sprinkler pipes and the tops of piles. Not less than three (3) feet clearance shall be left between walls and sides of piles. However, when the storage compartment is not more than thirty (30) feet in width, one (1) foot clearance at side walls shall be approved when a center aisle not less than five (5) feet wide is maintained.
(Ord. No. 991-49. Passed 6-27-49, eff. 6-27-49)
(a) Whenever the quantity of loose combustible fiber stored within a storage room within a building exceeds one thousand (1,000) cubic feet, such storage room shall be equipped with approved automatic sprinklers or other approved automatic or manually operated fire extinguishing equipment.
(b) Except when the quantity stored within any one (1) fire area is less than three hundred (300) cubic feet of baled combustible fiber, all storage rooms and warehouses for the storage of baled combustible fiber shall be equipped with approved automatic sprinklers or other approved automatic fire extinguishing equipment.
(Ord. No. 991-49. Passed 6-27-49, eff. 6-27-49)
Loading...