When the quantity of loose highly flammable materials stored exceeds 100 cubic feet, rooms separating such area from every other part of the building shall be required. Such rooms shall have separations providing the following fire-resistive ratings:
Quantity of Highly Flammable Materials | Fire-resistive Rating |
100.1 to 500 cubic feet | 1-hour |
500.1 to 2,500 cubic feet | 2-hour |
Exceeding 2,500 cubic feet | 4-hour |
Baled storage rooms shall comply with the following:
Quantity of Highly Flammable Materials | Fire-resistive Rating |
500 to 2,500 cubic feet | 1-hour |
2,500.1 to 5,000 cubic feet | 2-hour |
Exceeding 5,000 cubic feet | 4-hour |
(Prior code § 92-51)
Openings through fire-resistance rated construction shall be protected in accordance with Chapter 14B-7.
(Prior code § 92-52; Amend Coun. J. 10-7-20, p. 21791, Art. VI, § 86)
Every such room as required by Section 15-28-620 shall have at least one exterior wall open to a clear space of at least 15 feet.
(Prior code § 92-53)