Loading...
15-28-930 Drying boxes.
   Every box for the drying of nitrocellulose products shall be provided with one automatic sprinkler head for each 60 cubic feet of volume.
(Prior code §  92-82)
ARTICLE XVIII. NITROCELLULOSE (15-28-940 et seq.)
15-28-940 Safety clearances.
   Every nitrocellulose building shall be freestanding and isolated by a safety clearance computed at the rate of five feet per 1,000 pounds or fraction thereof of nitrocellulose manufactured or reclaimed; provided, however, that such safety clearance shall in no case be less than 50 feet; and provided further, that the requirements of this paragraph shall not apply to any buildings in which 25 pounds or less of nitrocellulose are manufactured or reclaimed during any 24-hour period.
(Prior code §  92-83)
15-28-950 Construction requirements.
   Every nitrocellulose building shall be of Type IA, IB, or II construction.
(Prior code § 92-84; Amend Coun. J. 10-7-20, p. 21791, Art. VI, § 94)
Loading...