The provisions of Section 509 of IBC are adopted by reference with the following modifications:
1. Replace Table 509 as shown:
TABLE 509
INCIDENTAL USES
INCIDENTAL USES
ROOM OR AREA
|
SEPARATION AND/OR PROTECTION
|
ROOM OR AREA
|
SEPARATION AND/OR PROTECTION
|
Furnace room where any piece of equipment is over 400,000 Btu per hour input | 2 hours |
Rooms with boilers where the largest piece of equipment is over 15 psi and 10 horsepower | 2 hours |
Furnace rooms and boiler rooms in buildings having an occupant load exceeding 200 persons | 2 hours |
Furnace rooms and boiler rooms in Group I occupancies | 2 hours |
Furnace rooms and boiler rooms in other than Group R-5 occupancies | 1 hour |
Refrigerant machinery room | 1 hour |
Hydrogen fuel gas rooms, not classified as Group H | 1 hour in Group B, F, M, S and U occupancies; 2 hours in Group A, E, I and R occupancies. |
Incinerator rooms | 2 hours and provide automatic sprinkler system |
Paint shops, not classified as Group H, located in occupancies other than Group F | 2 hours; or 1 hour and provide automatic sprinkler system |
In Group E occupancies, laboratories and vocational shops not classified as Group H | 1 hour |
In Group I-2 occupancies, laboratories not classified as Group H | 1 hour and provide automatic sprinkler system |
In ambulatory care facilities, laboratories not classified as Group H | 1 hour |
Laundry rooms over 100 square feet | 1 hour |
Group I-3 cells and Group I-2 patient rooms equipped with padded surfaces | 1 hour |
In Group I-2, physical plant maintenance shops | 1 hour |
Waste, recycling and linen collection rooms with containers that have an aggregate volume of 10 cubic feet or greater in ambulatory care facilities or Group I-2 occupancies | 1 hour |
Waste, recycling and linen collection rooms over 100 square feet | 1 hour |
Storage rooms over 100 square feet in ambulatory care facilities and Group A, E, I, R-1, R-2, R-3 or R-4 occupancies | 2 hours or 1 hour and provide automatic sprinkler system |
Storage rooms used for combustible material in buildings with an exhibition area | 2 hours and provide automatic sprinkler system |
Stationary storage battery systems having an energy capacity greater than the threshold quantity specified in the Chicago Fire Prevention Code | 1 hour in Group B, F, M, S and U occupancies; 2 hours in Group A, E, I and R occupancies. |
Telecommunication equipment areas over 50 square feet and not over 150 square feet | 2 hours or 1 hour and provide automatic sprinkler system |
Telecommunication equipment areas over 150 square feet | 2 hours a |
Electrical installations and transformers | See Sections 110.26 through 110.34 and Sections 450.8 through 450.48 of the Chicago Electrical Code for protection and separation requirements. |
For SI: 1 square foot = 0.0929 m
2, 1 pound per square inch (psi) = 6.9 kPa, 1 British thermal unit (Btu) per hour = 0.293 watts, 1 horsepower = 746 watts, 1 gallon = 3.785 L, 1 cubic foot = 0.0283 m
3.
a. Telecommunication equipment areas over 150 square feet require an automatic fire extinguishing system in accordance with section 903.2.11.7.
2. Revise the exception to Section 509.1 to read:
"Exception: Incidental uses within and serving a single dwelling unit or sleeping unit are not required to comply with this section."
3. Revise Section 509.3 to read:
"509.3 Area limitations.
Incidental uses shall not occupy more than 10 percent of the gross floor area of the primary occupancy in which they are located."
4. Delete the second sentence in Section 509.4.1.
5. Delete Section 509.4.2 and its subsections.
(Amend Coun. J. 2-19-20, p. 14473, Art. II, § 19; Amend Coun. J. 6-25-21, p. 32180, Art. II, § 8; Amend Coun. J. 12-14-22, p. 58278, Art. III, § 1)