The provisions of Section 505 of IBC are adopted by reference with the following modifications:
1. Revise Section 505.2 to read:
"505.2 Mezzanines.
A mezzanine or mezzanines in compliance with Section 505.2 shall be considered a portion of the story below. Such mezzanines shall not contribute to the number of stories above grade plane as regulated by Section 503.1. The area of the mezzanine shall be included in determining the building area and the fire area. The clear height above and below the mezzanine floor construction shall be not less than 7 feet (2134 mm)."
2. Revise Section 505.2.1 to read:
"505.2.1 Area limitation.
The aggregate area of a mezzanine or mezzanines within a room shall be not greater than twenty percent of the floor area of that room or space in which they are located. The enclosed portion of a room shall not be included in a determination of the floor area of the room in which the mezzanine is located. In determining the allowable mezzanine area, the area of the mezzanine shall not be included in the floor area of the room.
Exceptions:
1. The aggregate area of mezzanines in buildings of Type I or II construction for special industrial occupancies in accordance with Section 503.1.1 shall be not greater than two-thirds of the floor area of the room.
2. [Reserved.]
3. The aggregate area of a mezzanine within a dwelling unit that is located in a building equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2 shall not be greater than one-half of the floor area of the room, provided that both:
3.1. Except for enclosed closets and bathrooms, the mezzanine shall be open to the room in which such mezzanine is located.
3.2. The opening to the room shall be unobstructed except for walls not more than 48 inches (1219 mm) in height, columns and posts."
3. Revise Section 505.2.1.1 by replacing "two-thirds" with "one-half."
4. Revise the exceptions to Section 505.2.3 to read:
"1. In Group B, F, M and S occupancies in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, mezzanines or portions thereof are not required to be open to the room in which the mezzanines are located, provided that the occupant load of the aggregate area of the enclosed space is not greater than 10.
2. [Reserved.]
3. Mezzanines or portions thereof are not required to be open to the room in which the mezzanines are located provided that the aggregate floor area of the enclosed space is not greater than 10 percent of the allowable mezzanine area.
4. In industrial facilities, mezzanines used for control equipment are permitted to be glazed on all sides.
5. [Reserved.]
6. Mezzanines in accordance with Exception 3 to Section 505.2.1."
5. Revise Section 505.3 by replacing "stories" with "stories above grade plane."
6. Revise Section 505.3.1 by replacing "two-thirds" with "one-half."
(Amend Coun. J. 2-19-20, p. 14473, Art. II, § 17)
The provisions of Section 506 of IBC are adopted by reference with the following modifications:
1. Revise Section 506.1 and its subsections to read:
"506.1 General.
The allowable building area of a building shall be determined based on the type of construction, occupancy classification, whether there is an automatic sprinkler system installed throughout the building and the amount of building frontage on a public way or yard.
506.1.1 [Reserved.]
506.1.2 [Reserved.]
506.1.3 Basements.
Basements shall be included in building area where the total area of such basements exceeds the allowable building area for a one-story above grade plane building of the same occupancy and construction type.
506.1.3.1 Maximum area.
Every basement exceeding 40,000 square feet (3716 m2) in area shall be subdivided by fire barriers into areas not exceeding 40,000 square feet (3716 m2), provided where the building is equipped throughout with an automatic sprinkler system, the maximum undivided area may be increased to 80,000 square feet (7432 m2)."
2. Replace Table 506.2 as shown:
TABLE 506.2
ALLOWABLE AREA FACTOR (At = NS, S1, S13R, S13D or SM, as applicable) IN SQUARE FEET a, b
ALLOWABLE AREA FACTOR (At = NS, S1, S13R, S13D or SM, as applicable) IN SQUARE FEET a, b
OCCUPANCY CLASSIFICATION
|
SEE NOTES
|
CONSTRUCTION TYPE
| ||||||||
TYPE I
|
TYPE II
|
TYPE III
|
TYPE IV
|
TYPE V
| ||||||
A
|
B
|
A
|
B
|
A
|
B
|
HT
|
A
|
B
|
OCCUPANCY CLASSIFICATION
|
SEE NOTES
|
CONSTRUCTION TYPE
| ||||||||
TYPE I
|
TYPE II
|
TYPE III
|
TYPE IV
|
TYPE V
| ||||||
A
|
B
|
A
|
B
|
A
|
B
|
HT
|
A
|
B
| ||
A-1 | NS | UL | UL | 16,000 | 8,500 | 6,000 | NP | 6,000 | 3,000 | NP |
S1 | UL | UL | 64,000 | 34,000 | 24,000 | 12,000 | 24,000 | 12,000 | NP | |
SM | UL | UL | 48,000 | 25,500 | 18,000 | 9,000 | 18,000 | 9,000 | NP | |
A-2 | NS | UL | UL | 16,000 | 8,500 | 6,000 | 5,000 | 6,000 | 3,000 | NP |
S1 | UL | UL | 64,000 | 34,000 | 24,000 | 20,000 | 24,000 | 12,000 | NP | |
SM | UL | UL | 48,000 | 25,500 | 18,000 | 15,000 | 18,000 | 9,000 | NP | |
A-3 | NS | UL | UL | 16,000 | 8,500 | 6,000 | 5,000 | 6,000 | 3,000 | NP |
S1 | UL | UL | 64,000 | 34,000 | 24,000 | 20,000 | 24,000 | 12,000 | NP | |
SM | UL | UL | 48,000 | 25,500 | 18,000 | 15,000 | 18,000 | 9,000 | NP | |
A-4 | NS | UL | UL | 16,000 | 8,500 | 6,000 | 5,000 | 6,000 | 3,000 | NP |
S1 | UL | UL | 64,000 | 34,000 | 24,000 | 20,000 | 24,000 | 12,000 | NP | |
SM | UL | UL | 48,000 | 25,500 | 18,000 | 15,000 | 18,000 | 9,000 | NP | |
A-5 | NS | UL | UL | UL | UL | UL | UL | UL | UL | UL |
S1 | UL | |||||||||
SM | UL | |||||||||
B | NS | UL | UL | 20,000 | 6,000 | 10,000 | 8,000 | 10,000 | 6,000 | 4,000 |
S1 | UL | UL | UL | UL | UL | 32,000 | 40,000 | 24,000 | 16,000 | |
SM | UL | UL | 60,000 | 18,000 | 30,000 | 24,000 | 30,000 | 18,000 | NP | |
E-1 | NS | UL | UL | 16,000 | 5,000 | 8,000 | 3,000 | 10,000 | 3,000 | NP |
S1 | UL | UL | 64,000 | 20,000 | 32,000 | 12,000 | 40,000 | 12,000 | NP | |
SM | UL | UL | 48,000 | 15,000 | 24,000 | 9,000 | 30,000 | 9,000 | NP | |
E-2 | NS | UL | UL | 16,000 | 5,000 | 8,000 | 3,000 | 10,000 | 3,000 | NP |
S1 | UL | UL | 64,000 | 20,000 | 32,000 | 12,000 | 40,000 | 12,000 | NP | |
SM | UL | UL | 48,000 | 15,000 | 24,000 | 9,000 | 30,000 | 9,000 | NP | |
F-1 | NS | UL | UL | 16,000 | 4,000 | 8,000 | 4,000 | 8,000 | 5,000 | 3,000 |
S1 | UL | UL | UL | UL | 32,000 | 16,000 | 32,000 | 20,000 | 12,000 | |
SM | UL | UL | 48,000 | 12,000 | 24,000 | 12,000 | 24,000 | 15,000 | NP | |
F-2 | NS | UL | UL | 20,000 | 10,000 | 10,000 | 6,000 | 10,000 | 6,000 | 4,000 |
S1 | UL | UL | UL | UL | 40,000 | 24,000 | 40,000 | 24,000 | 16,000 | |
SM | UL | UL | 60,000 | 30,000 | 30,000 | 18,000 | 30,000 | 18,000 | NP | |
H-1 | NS c, d | 21,000 | 16,500 | 11,000 | 6,000 | 9,500 | 5,000 | 10,500 | 5,000 | NP |
S1 | 21,000 | 16,500 | 11,000 | 6,000 | 9,500 | 5,000 | 10,500 | 5,000 | NP | |
SM | NP | NP | NP | NP | NP | NP | NP | NP | NP | |
H-2 | NS c, d | 21,000 | 16,500 | 11,000 | 6,000 | 9,500 | 5,000 | 10,500 | NP | NP |
S1 | 21,000 | 16,500 | 11,000 | 6,000 | 9,500 | 5,000 | 10,500 | NP | NP | |
SM | 42,000 | 16,500 | 11,000 | NP | 9,500 | NP | NP | NP | NP | |
H-3 | NS c, d | UL | 60,000 | 20,000 | 6,000 | 10,000 | 5,000 | 10,000 | NP | NP |
S1 | UL | 60,000 | 20,000 | 6,000 | 10,000 | 5,000 | 10,000 | NP | NP | |
SM | UL | 60,000 | 20,000 | NP | 10,000 | 5,000 | 10,000 | NP | NP | |
H-4 | NS c, d | UL | UL | 20,000 | 6,000 | 10,000 | 8,000 | 10,000 | 6,000 | NP |
S1 | UL | UL | 80,000 | 24,000 | 40,000 | 32,000 | 40,000 | 24,000 | NP | |
SM | UL | UL | 60,000 | NP | 30,000 | 24,000 | 30,000 | NP | NP | |
H-5 | NS c, d | UL | UL | 16,000 | 4,000 | 8,000 | 4,000 | 8,000 | NP | NP |
S1 | UL | UL | 64,000 | 16,000 | 32,000 | 16,000 | 32,000 | NP | NP | |
SM | UL | UL | 48,000 | NP | 24,000 | 12,000 | 24,000 | NP | NP | |
I-1 | NS d, e | UL | 55,000 | 16,000 | 4,000 | 6,000 | 4,000 | 6,000 | 3,000 | NP |
S1 | UL | 220,000 | 64,000 | 16,000 | 24,000 | 16,000 | 24,000 | 12,000 | NP | |
SM | UL | 165,000 | 48,000 | 12,000 | 18,000 | 12,000 | 18,000 | 9,000 | NP | |
I-2 | NS d, f | UL | UL | 12,000 | 6,000 | 6,000 | NP | 6,000 | 3,000 | NP |
S1 | UL | UL | 48,000 | 24,000 | 24,000 | NP | 24,000 | 12,000 | NP | |
SM | UL | UL | 36,000 | NP | NP | NP | NP | 9,000 | NP | |
I-3 | NS d, e | UL | UL | 12,000 | 6,000 | 6,000 | NP | 6,000 | 3,000 | NP |
S1 | UL | UL | 48,000 | 24,000 | 24,000 | NP | 24,000 | 12,000 | NP | |
SM | UL | UL | 36,000 | NP | NP | NP | NP | 9,000 | NP | |
I-4 | NS d, g | UL | 55,000 | 16,000 | 4,000 | 6,000 | 4,000 | 6,000 | 3,000 | NP |
S1 | UL | 220,000 | 64,000 | 16,000 | 24,000 | 16,000 | 24,000 | 12,000 | NP | |
SM | UL | 165,000 | 48,000 | 12,000 | 18,000 | 12,000 | 18,000 | 9,000 | NP | |
M | NS | UL | UL | 16,000 | 6,000 | 8,000 | 6,000 | 8,000 | 5,000 | 3,000 |
S1 | UL | UL | UL | UL | UL | 24,000 | 32,000 | 20,000 | 12,000 | |
SM | UL | UL | 48,000 | 18,000 | 24,000 | 18,000 | 24,000 | 15,000 | NP | |
R-1 h | NS d | UL | UL | 24,000 | 10,000 | 10,000 | 8,000 | 10,000 | 5,000 | 3,000 |
S13R | UL | UL | 48,000 | 20,000 | 20,000 | 16,000 | 20,000 | 10,000 | 6,000 | |
S1 | UL | UL | 96,000 | 40,000 | 40,000 | 32,000 | 40,000 | 20,000 | 12,000 | |
SM | UL | UL | 72,000 | 30,000 | 30,000 | 24,000 | 30,000 | 15,000 | 9,000 | |
R-2 | NS | UL | UL | 24,000 | 10,000 | 10,000 | 8,000 | 10,000 | 5,000 | 3,000 |
S13R | UL | UL | 48,000 | 20,000 | 20,000 | 16,000 | 20,000 | 10,000 | 6,000 | |
S1 | UL | UL | 96,000 | 40,000 | 40,000 | 32,000 | 40,000 | 20,000 | 12,000 | |
SM | UL | UL | 72,000 | 30,000 | 30,000 | 24,000 | 30,000 | 15,000 | 9,000 | |
R-3 h | NS | UL | UL | 24,000 | 10,000 | 10,000 | 8,000 | 10,000 | 5,000 | 3,000 |
S13D | UL | UL | 48,000 | 20,000 | 20,000 | 16,000 | 20,000 | 10,000 | 6,000 | |
S13R | UL | UL | 48,000 | 20,000 | 20,000 | 16,000 | 20,000 | 10,000 | 6,000 | |
S1 | UL | UL | 96,000 | 40,000 | 40,000 | 32,000 | 40,000 | 20,000 | 12,000 | |
SM | UL | UL | 72,000 | 30,000 | 30,000 | 24,000 | 30,000 | 15,000 | 9,000 | |
R-4 h | NS d | UL | UL | 24,000 | 10,000 | 10,000 | 8,000 | 10,000 | 5,000 | 3,000 |
S13D | UL | UL | 48,000 | 20,000 | 20,000 | 16,000 | 20,000 | 10,000 | 6,000 | |
S13R | UL | UL | 48,000 | 20,000 | 20,000 | 16,000 | 20,000 | 10,000 | 6,000 | |
S1 | UL | UL | 96,000 | 40,000 | 40,000 | 32,000 | 40,000 | 20,000 | 12,000 | |
SM | UL | UL | 72,000 | 30,000 | 30,000 | 24,000 | 30,000 | 15,000 | 9,000 | |
R-5 | NS | UL | UL | 24,000 | 10,000 | 10,000 | 8,000 | 10,000 | 5,000 | 3,000 |
S13D | UL | UL | 48,000 | 20,000 | 20,000 | 16,000 | 20,000 | 10,000 | 6,000 | |
S13R | UL | UL | 48,000 | 20,000 | 20,000 | 16,000 | 20,000 | 10,000 | 6,000 | |
S1 | UL | UL | 96,000 | 40,000 | 40,000 | 32,000 | 40,000 | 20,000 | 12,000 | |
SM | UL | UL | 72,000 | 30,000 | 30,000 | 24,000 | 30,000 | 15,000 | 9,000 | |
S-1 | NS | UL | 35,500 | 19,000 | 8,500 | 14,000 | 8,000 | 18,000 | 5,000 | 3,000 |
S1 | UL | UL | UL | UL | 56,000 | 32,000 | 72,000 | 20,000 | 12,000 | |
SM | UL | 106,500 | 57,000 | 25,500 | 42,000 | 24,000 | 54,000 | 15,000 | NP | |
S-2 | NS | UL | 79,000 | 28,500 | 13,000 | 21,000 | 10,000 | 27,000 | 6,000 | 4,000 i |
S1 | UL | UL | UL | UL | 84,000 | 40,000 | 108,000 | 24,000 | 16,000 i | |
SM | UL | 237,000 | 85,500 | 39,000 | 63,000 | 30,000 | 81,000 | 18,000 | NP | |
U | NS | UL | 30,000 | 16,000 | 6,000 | 8,000 | 6,000 | 8,000 | 5,000 | 1,000 |
S1 | UL | 120,000 | 64,000 | 24,000 | 32,000 | 24,000 | 32,000 | 20,000 | 4,000 | |
SM | UL | 90,000 | 48,000 | 18,000 | 24,000 | 18,000 | 24,000 | 15,000 | NP | |
For SI: 1 square foot = 0.0929 m
2.
UL = Unlimited.
NP = Not permitted.
NS = Buildings not equipped throughout with an automatic sprinkler system.
S1 = Buildings a maximum of one story above grade plane equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1.
SM = Buildings two or more stories above grade plane equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1.
S13R = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.2.
S13D = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.3.
a. See Chapters 4 and 5 for specific exceptions to the allowable area factor in this table.
b. See Section 903.2 for the minimum thresholds for protection by an automatic sprinkler system for specific occupancies.
c. New Group H occupancies are required to be protected by an automatic sprinkler system in accordance with Section 903.2.5.
d. The NS value is only for use in evaluation of existing buildings in accordance with the Chicago Building Rehabilitation Code.
e. New Group I-1 and I-3 occupancies are required to be protected by an automatic sprinkler system in accordance with Section 903.2.6. For new Group I-1 occupancies, Condition 1, see Exception 1 of Section 903.2.6.
f. New and existing Group I-2 occupancies are required to be protected by an automatic sprinkler system in accordance with Section 903.2.6 and Section 1103.5 of the Chicago Fire Prevention Code.
g. New Group I-4 occupancies see Exceptions 2 and 3 of Section 903.2.6.
h. New Group R-1, R-3 and R-4 occupancies are required to be protected by an automatic sprinkler system in accordance with Section 903.2.8.
i. Type VB construction is not allowed for motor-vehicle-related occupancies other than private garages.
3. Revise Equation 5-2 by deleting the second sentence from the description of Sa.
4. Revise Section 506.2.4 to read:
"506.2.4 Mixed-occupancy, multistory buildings.
Each story of a mixed-occupancy building with more than one story above grade plane shall individually comply with the applicable requirements of Section 508.1. For buildings with more than three stories above grade plane, the building area shall be such that the aggregate sum of the ratios of the actual floor area of each story divided by the allowable area of such stories, determined in accordance with Equation 5-3 based on the applicable provisions of Section 508.1, shall not exceed three."
5. Delete the exception to Section 506.2.4.
6. Revise Section 506.3 to replace "public way" with "public way."
7. Revise Section 506.3.1 to read:
"506.3.1 Minimum percentage of perimeter.
To qualify for an area factor increase based on frontage, a building shall have not less than 25 percent of its perimeter abut a public way, court or yard. Such court or yard shall be either on the same lot or dedicated for public use and shall have direct access, not less than 20 feet (6096 mm) wide, from a public way."
8. Revise Section 506.3.2 to read:
"506.3.2 Minimum frontage distance.
To qualify for an area factor increase based on frontage, the public way, court or yard adjacent to the building perimeter shall have a minimum distance (W) of 20 feet (6096 mm) measured at right angles from the building face to any of the following:
1. The closest abutting property line.
2. The far side of a public way.
3. The exterior face of an adjacent building on the same lot.
4. The opposite side of a court.
Where the value of W is greater than 30 feet (9144 mm), a value of 30 feet (9144 mm) shall be used in calculating the area factor increase based on frontage, regardless of the actual width of the public way, court or yard. Where the value of W varies along the perimeter of the building, the calculation performed in accordance with Equation 5-5 shall be based on the weighted average calculated in accordance with Equation 5-4."
9. Revise the definitions of values for Equation 5-4 by replacing "public way or open space" with "public way, court or yard" and inserting "but not greater than 30 feet (9144 mm)" at the end of the definition of Wn
.
10. Delete the exception to Section 506.3.2.
11. Revise Equation 5-5 to read:
"If = (F/P)(W/30)(S) (Equation 5-5)
where:
If = Area factor increase due to frontage.
F = Building perimeter that fronts on a public way or yard having a minimum width of 20 feet (6096 mm) (feet).
P = Perimeter of entire building (feet).
W = Width of public way or yard (feet) in accordance with Section 506.3.2.
S = Where building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, S = 2; where building is not equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2, S = 1.
(Amend Coun. J. 7-24-19, p. 3646, § 30; Amend Coun. J. 10-7-20, p. 21791, Art. II, § 7; Amend Coun. J. 6-25-21, p. 32180, Art. II, § 6)
The provisions of Section 508 of IBC are adopted by reference with the following modifications:
1. Delete exception 1 to Section 508.1.
1.1. Revise exception 2 to Section 508.1 by replacing "Table 415.6.2" with "the Chicago Fire Prevention Code."
2. Revise Section 508.2.2 to read:
"508.2.2 Allowable building height.
The allowable building height and number of stories above grade plane of the building containing accessory occupancies shall be in accordance with Section 504 for the main occupancy of the building."
3. Revise Section 508.2.3 to read:
"508.2.3 Allowable building area.
The allowable area of the building shall be based on the applicable provisions of Section 506 for the main occupancy of the building. Aggregate accessory occupancies shall not occupy more than 25 percent of the floor area of the story nor more than 10 percent of the total floor area of the main occupancy in which they are located and shall not exceed the tabular area values for nonsprinklered buildings in Table 506.2 for each such accessory occupancy.
Exception: The building official and fire code official may jointly approve accessory occupancies exceeding the 10 percent and 25 percent limits when in their opinion such accessory occupancies do not unduly increase the hazard."
4. Revise the exceptions to Section 508.2.4 to read:
"Exceptions:
1. Group H occupancies shall not be classified as accessory occupancies and shall be separated from all other occupancies in accordance with Section 508.4.
2. Group I-1, R-1, R-2, R-3, R-4 and R-5 dwelling units and sleeping units shall not be classified as accessory occupancies and shall be separated from other dwelling or sleeping units and from other occupancies contiguous to them in accordance with the requirements of Section 420.
3. Motor-vehicle-related occupancies shall not be classified as accessory occupancies and shall be separated from other occupancies in accordance with Section 406."
5. Revise Section 508.3.2 to read:
"508.3.2 Allowable building area, height and number of stories above grade plane.
The allowable building area, building height and number of stories above grade plane of the building or portion thereof shall be based on the most restrictive allowances for the occupancy groups under consideration for the type of construction of the building in accordance with Section 503.1."
6. Revise the exceptions to Section 508.3.3 to read:
"Exceptions:
1. Group H occupancies shall be separated from all other occupancies in accordance with Section 508.4.
2. Group I-1, R-1, R-2, R-3, R-4 and R-5 dwelling units and sleeping units shall be separated from other dwelling or sleeping units and from other occupancies contiguous to them in accordance with the requirements of Section 420.
3. Group A occupancies with an aggregate occupant load of 300 or more persons shall be separated from other main occupancies by construction providing a fire-resistance rating of not less than 2 hours in buildings that are not protected throughout by an automatic sprinkler system in accordance with Section 903.3.1.1.
4. Group A occupancies with an aggregate occupant load of less than 300 persons shall be separated from other main occupancies by construction providing a fire-resistance rating of not less than 1 hour in buildings that are not protected throughout by an automatic sprinkler system in accordance with Section 903.3.1.1.
5. Motor-vehicle-related occupancies shall be separated from other occupancies in accordance with Section 406."
7. Replace Table 508.4 as shown:
TABLE 508.4
REQUIRED SEPARATION OF OCCUPANCIES (HOURS) f
REQUIRED SEPARATION OF OCCUPANCIES (HOURS) f
OCCUPANCY
|
A, E
| I-1 a, I-3, I-4 | I-2 | R a |
F-2, S-2 b, U | B e, M | F-1, S-1 | H-1 | H-2 | H-3, H-4 | H-5
| |||||||||||
S
|
NS
|
S
|
NS
|
S
|
NS
|
S
|
NS
|
S
|
NS
|
S
|
NS
|
S | NS | S
|
NS
|
S
|
NS
|
S
|
NS
|
S
|
NS
|
OCCUPANCY
|
A, E
| I-1 a, I-3, I-4 | I-2 | R a |
F-2, S-2 b, U | B e, M | F-1, S-1 | H-1 | H-2 | H-3, H-4 | H-5
| |||||||||||
S
|
NS
|
S
|
NS
|
S
|
NS
|
S
|
NS
|
S
|
NS
|
S
|
NS
|
S | NS | S
|
NS
|
S
|
NS
|
S
|
NS
|
S
|
NS
| |
A, E | N h | N g, h | 2 | 3 | 3 | NP | 1 h | 2 | 1 h | 2 | 1 h | 2 | 1 h | 2 | NP | NP | 4 | NP | 4 | NP | 4 | NP |
I-1 a, I-3, I-4 | – | – | N | N | 2 | NP | 2 | NP | 3 | 4 | 3 | 4 | 3 | 4 | NP | NP | 4 | NP | 4 | NP | 4 | NP |
I-2 | – | – | – | – | N | N | 2 | NP | 3 | NP | 2 | NP | 2 | NP | NP | NP | 4 | NP | 4 | NP | 4 | NP |
R a | – | – | – | – | – | – | N | N | 1 | 2 | 1 | 2 | 1 | 2 | NP | NP | 4 | NP | 4 | NP | 4 | NP |
F-2, S-2 b, U | – | – | – | – | – | – | – | – | N | N | 1 | 2 | 1 | 2 | NP | NP | 3 | 4 | 4 | 4 | 4 | NP |
B e, M | – | – | – | – | – | – | – | – | – | – | N | N | 1 | 2 | NP | NP | 3 | 4 | 4 | 4 | 3 | NP |
F-1, S-1 | – | – | – | – | – | – | – | – | – | – | – | – | N | N | NP | NP | 3 | 4 | 4 | 4 | 3 | NP |
H-1 | – | – | – | – | – | – | – | – | – | – | – | – | – | – | N | NP | NP | NP | NP | NP | NP | NP |
H-2 | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | N | NP | 2 | NP | 1 | NP |
H-3, H-4 | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | 2 d | NP | 1 | NP |
H-5 | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | N | NP |
S = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1.
NS = Buildings not equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1.
N = No separation requirement.
NP = Not Permitted.
a. See Section 420.
b. The required separation from parking garages and other motor-vehicle-related occupancies shall be in accordance with Section 406.
c. [Reserved.]
d. Separation is not required between occupancies of the same classification.
e. See Section 422.2 for ambulatory care facilities.
f. Occupancy separations that serve to define fire area limits established in Chapter 9 for requiring fire protection systems shall also comply with Section 707.3.10 and Table 707.3.10 in accordance with Section 901.7.
g. Group A occupancies with an aggregate occupant load of less than 300 persons shall be separated from other occupancies by construction providing a fire-resistance rating of not less than one 1 hour in buildings that are not protected throughout by an automatic sprinkler system in accordance with Section 903.3.1.1.
h. Group A occupancies with an aggregate occupant load of 300 or more persons shall be separated from other occupancies by construction providing a fire-resistance rating of not less than 2 hours in buildings that are not protected throughout by an automatic sprinkler system in accordance with Section 903.3.1. 1.
8. Revise Section 508.4.3, including the exception, to read:
"508.4.3 Allowable building height and number of stories above grade plane.
Each separated occupancy shall comply with the building height limitations and story above grade plane limitations based on the type of construction of the building in accordance with Section 503.1."
(Amend Coun. J. 2-19-20, p. 14473, Art. II, § 18; Amend Coun. J. 10-7-20, p. 21791, Art. II, § 8; Amend Coun. J. 6-25-21, p. 32180, Art. II, § 7; Amend Coun. J. 1-26-22, p. 43756, Art. II, § 5; Amend Coun. J. 1-24-24, p. 8634, Art. IV, § 1)
The provisions of Section 509 of IBC are adopted by reference with the following modifications:
1. Replace Table 509 as shown:
TABLE 509
INCIDENTAL USES
INCIDENTAL USES
ROOM OR AREA
|
SEPARATION AND/OR PROTECTION
|
ROOM OR AREA
|
SEPARATION AND/OR PROTECTION
|
Furnace room where any piece of equipment is over 400,000 Btu per hour input | 2 hours |
Rooms with boilers where the largest piece of equipment is over 15 psi and 10 horsepower | 2 hours |
Furnace rooms and boiler rooms in buildings having an occupant load exceeding 200 persons | 2 hours |
Furnace rooms and boiler rooms in Group I occupancies | 2 hours |
Furnace rooms and boiler rooms in other than Group R-5 occupancies | 1 hour |
Refrigerant machinery room | 1 hour |
Hydrogen fuel gas rooms, not classified as Group H | 1 hour in Group B, F, M, S and U occupancies; 2 hours in Group A, E, I and R occupancies. |
Incinerator rooms | 2 hours and provide automatic sprinkler system |
Paint shops, not classified as Group H, located in occupancies other than Group F | 2 hours; or 1 hour and provide automatic sprinkler system |
In Group E occupancies, laboratories and vocational shops not classified as Group H | 1 hour |
In Group I-2 occupancies, laboratories not classified as Group H | 1 hour and provide automatic sprinkler system |
In ambulatory care facilities, laboratories not classified as Group H | 1 hour |
Laundry rooms over 100 square feet | 1 hour |
Group I-3 cells and Group I-2 patient rooms equipped with padded surfaces | 1 hour |
In Group I-2, physical plant maintenance shops | 1 hour |
Waste, recycling and linen collection rooms with containers that have an aggregate volume of 10 cubic feet or greater in ambulatory care facilities or Group I-2 occupancies | 1 hour |
Waste, recycling and linen collection rooms over 100 square feet | 1 hour |
Storage rooms over 100 square feet in ambulatory care facilities and Group A, E, I, R-1, R-2, R-3 or R-4 occupancies | 2 hours or 1 hour and provide automatic sprinkler system |
Storage rooms used for combustible material in buildings with an exhibition area | 2 hours and provide automatic sprinkler system |
Stationary storage battery systems having an energy capacity greater than the threshold quantity specified in the Chicago Fire Prevention Code | 1 hour in Group B, F, M, S and U occupancies; 2 hours in Group A, E, I and R occupancies. |
Telecommunication equipment areas over 50 square feet and not over 150 square feet | 2 hours or 1 hour and provide automatic sprinkler system |
Telecommunication equipment areas over 150 square feet | 2 hours a |
Electrical installations and transformers | See Sections 110.26 through 110.34 and Sections 450.8 through 450.48 of the Chicago Electrical Code for protection and separation requirements. |
For SI: 1 square foot = 0.0929 m
2, 1 pound per square inch (psi) = 6.9 kPa, 1 British thermal unit (Btu) per hour = 0.293 watts, 1 horsepower = 746 watts, 1 gallon = 3.785 L, 1 cubic foot = 0.0283 m
3.
a. Telecommunication equipment areas over 150 square feet require an automatic fire extinguishing system in accordance with section 903.2.11.7.
2. Revise the exception to Section 509.1 to read:
"Exception: Incidental uses within and serving a single dwelling unit or sleeping unit are not required to comply with this section."
3. Revise Section 509.3 to read:
"509.3 Area limitations.
Incidental uses shall not occupy more than 10 percent of the gross floor area of the primary occupancy in which they are located."
4. Delete the second sentence in Section 509.4.1.
5. Delete Section 509.4.2 and its subsections.
(Amend Coun. J. 2-19-20, p. 14473, Art. II, § 19; Amend Coun. J. 6-25-21, p. 32180, Art. II, § 8; Amend Coun. J. 12-14-22, p. 58278, Art. III, § 1)