Skip to code content (skip section selection)
Compare to:
Chicago Overview
Prior Chicago Building Code
BUILDING CODE AND RELATED EXCERPTS OF THE MUNICIPAL CODE OF CHICAGO
DIVISION 1 - ADMINISTRATION
DIVISION 2 - DEFINITIONS
DIVISION 3 - USE AND OCCUPANCY CLASSIFICATIONS
DIVISION 4 - SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY
DIVISION 5 - GENERAL BUILDING HEIGHTS AND AREAS
DIVISION 6 - TYPES OF CONSTRUCTION
DIVISION 7 - FIRE-RESISTANCE-RATED CONSTRUCTION
DIVISION 8 - INTERIOR FINISHES (NA)
DIVISION 9 - FIRE PROTECTION SYSTEMS
DIVISION 10 - MEANS OF EGRESS
DIVISION 11 - ACCESSIBILITY
DIVISION 12 - INTERIOR ENVIRONMENT
DIVISION 13 - ENERGY EFFICIENCY AND ENVIRONMENTAL PROTECTION
DIVISION 14 - EXTERIOR WALLS (NA)
DIVISION 15 - ROOF ASSEMBLIES AND ROOFTOP STRUCTURES (NA)
DIVISION 16 - STRUCTURAL DESIGN
DIVISION 17 - STRUCTURAL TESTS AND SPECIAL INSPECTIONS
DIVISION 18 - SOILS AND FOUNDATIONS
DIVISION 19 - CONCRETE
DIVISION 20 - ALUMINUM (NA)
DIVISION 21 - MASONRY
DIVISION 22 - STEEL
DIVISION 23 - WOOD
DIVISION 24 - GLASS AND GLAZING (NA)
DIVISION 25 - GYPSUM BOARD AND PLASTER (NA)
DIVISION 26 - PLASTIC (NA)
DIVISION 27 - ELECTRICAL
DIVISION 28 - MECHANICAL SYSTEMS
DIVISION 29 - PLUMBING SYSTEMS
DIVISION 30 - ELEVATORS AND CONVEYING SYSTEMS
DIVISION 31 - SPECIAL CONSTRUCTION (NA)
DIVISION 32 - ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
DIVISION 33 - SAFEGUARDS DURING CONSTRUCTION
DIVISION 34 - EXISTING STRUCTURES
Subdivision 3401 - General
CHAPTER 13-196 EXISTING BUILDINGS - MINIMUM REQUIREMENTS
13-196-010 Application.
13-196-020 Occupancy.
13-196-030 Structural stability.
13-196-031 Maintenance of exterior walls and enclosures - Definitions.
13-196-032 Maintenance of exterior walls and enclosures - Application.
13-196-033 Maintenance of exterior walls and enclosures - Critical examinations.
13-196-034 Maintenance of exterior walls and enclosures - Ongoing inspection and repair program.
13-196-035 Maintenance of exterior walls and enclosures - Reporting.
13-196-036 Maintenance of exterior walls - Retention of records at the building.
13-196-036.5 Reserved.
13-196-037 Maintenance of exterior walls and enclosures - Unsafe exterior walls and enclosures.
13-196-038 Rules and regulations.
13-196-038.5 Reserved.
13-196-039 Fines and penalties.
13-196-040 Floor loading.
13-196-050 Exit requirements.
13-196-060 Exits - Generally.
13-196-070 Exits - Types.
13-196-080 Passageways and exits to be unobstructed.
13-196-084 Stairwell re-entry in existing buildings.
13-196-085 Stairwell identification.
13-196-086 Area of rescue assistance identification.
13-196-090 Exit, stairway, fire escape and directional signs.
13-196-100 Smoke alarms - Where required.
13-196-110 Smoke alarms - Installation near sleeping rooms and in living levels.
13-196-120 Smoke alarms - Interior stairwell installation.
13-196-130 Smoke alarms - Standards.
13-196-140 Smoke alarms - Owner/tenant responsibilities.
13-196-150 Smoke alarms - Unlawful acts.
13-196-160 Reserved.
13-196-165 Carbon monoxide detectors.
13-196-170 Self-closing devices required for corridor doors.
13-196-180 Sprinkler systems - Where required.
13-196-190 Standpipe systems - Where required.
13-196-200 Standard fire alarm system requirements.
13-196-203 Life safety data sheet - Required.
13-196-204 Voice communication systems in existing buildings.
13-196-205 Automatic sprinkler system installation in existing high-rise buildings.
13-196-206 Life safety evaluation of existing high- rise buildings.
13-196-207 Materials and installation standards for retrofit fire protection systems.
13-196-208 Smokeproof towers in existing high- rise buildings - Fire shields.
13-196-209 High-rise buildings - Stairways - Doors - Frames.
13-196-210 High rise fire systems - Hotels.
13-196-220 Class II standard fire alarm systems.
13-196-230 Floor area and height.
13-196-240 Automatic fire detectors - Where required.
13-196-250 Permitted omission of sprinklers, heat and smoke detectors.
13-196-260 Fire extinguishers.
13-196-270 Elevator recall.
13-196-271 Continued operation.
13-196-280 Reserved.
13-196-290 Pre-ordinance hotels.
13-196-300 Institutional units.
13-196-310 Roominghouses.
13-196-320 Roominghouses - Sanitary facilities.
13-196-330 Roominghouses - Responsibility of operator.
13-196-340 Minimum requirements for residential buildings - General.
13-196-350 Residential buildings - Water closet.
13-196-360 Residential buildings - Lavatory.
13-196-370 Residential buildings - Bathtub or shower.
13-196-380 Residential buildings - Limitations on sharing sanitary facilities.
13-196-390 Residential buildings - Kitchen sink.
13-196-400 Residential buildings - Heating facilities.
13-196-410 Residential buildings - Heat to be furnished.
13-196-420 Residential buildings - Cold and hot water lines.
13-196-430 Residential buildings - Hot water to be furnished.
13-196-440 Gas-fired appliances.
13-196-450 Residential buildings - Hall and stairway lighting.
13-196-460 Residential buildings - Storage beneath stairways.
13-196-470 Residential buildings - Space, use and location - Applicability of provisions.
13-196-480 Residential buildings - Space requirements.
13-196-490 Residential buildings - Space requirements - Sleeping rooms.
13-196-500 Residential buildings - Access to water closets.
13-196-510 Residential buildings - Ceiling heights.
13-196-520 Residential buildings - Basement units.
13-196-530 Residential buildings - Foundations, exterior walls and roofs - Maintenance.
13-196-540 Residential buildings - Floors, interior walls and ceilings - Maintenance.
13-196-550 Residential buildings - Windows, doors and hatchways - Maintenance.
13-196-560 Residential buildings - Screens.
13-196-570 Residential buildings - Stairways and porches - Maintenance.
13-196-580 Residential buildings - Basements and cellars - Maintenance.
13-196-590 Residential buildings - Facilities, equipment, chimneys - Maintenance.
13-196-600 Residential buildings - Lot grading and drainage.
13-196-610 Residential buildings - Responsibilities of owners and occupants - General.
13-196-620 Residential buildings - Responsibilities of occupants.
13-196-630 Residential buildings - Responsibilities of owner or operator.
13-196-640 Residential buildings - Liability to city.
13-196-641 Application of certain sections.
13-196-650 Pre-ordinance conversion to existing buildings - Applicability.
13-196-660 Conversion of pre-ordinance buildings - Height limits.
13-196-670 Stairwells.
13-196-680 Corridors.
13-196-690 Dwelling separations.
13-196-700 Partitions.
13-196-710 Basement ceiling construction.
13-196-720 Heating plants.
13-196-730 Light and ventilation.
13-196-740 One additional dwelling unit over original allowed - Conditions.
13-196-750 Heat required.
13-196-760 Endangering health of employees.
Subdivision 3403 - Additions, Alterations or Repairs
DIVISION 35 - REFERENCED STANDARDS

You are viewing an archived code

Loading...
13-196-170  Self-closing devices required for corridor doors.
   In residential buildings exceeding four stories in height, all apartment doors opening upon public corridors shall be equipped with approved self-closing devices. In all new and existing single-room occupancy buildings, irrespective of height, all dwelling unit doors opening to public corridors shall be equipped with approved self-closing devices.
(Prior code § 78-16; Amend Coun. J. 5-4-94, p. 49750)
13-196-180  Sprinkler systems – Where required.
   The following existing buildings or structures, or parts thereof, are to be equipped with sprinkler systems complying with the requirements of Chapter 15-16:
   (a)   Every building of construction Type III or IV and of two stories or more in height, used in part or in whole as a Type I school, hospital, infirmary, nursery, orphanage, sheltered-care home, sanitoria or home for the aged or used in whole as a Type II school;
   (b)   Every building used in whole or in part as a men's cubicle hotel which does not comply with Section 13-64-020(a) of this Code;
   (c)   Every building used primarily as an exhibition area or in that portion of any building used as an exhibition area;
   (d)   Every building used in whole or in part as a nursing home, as defined, in Section 13-4-010.
   (e)   Areas used for storage of combustible containers in new and existing buildings, with exhibition areas, shall be enclosed with a two-hour fire resistive construction, and shall be equipped with a standard sprinkler system, as defined in Chapter 15-16 of this Code.
(Prior code § 78-17; Amend Coun. J. 5-9-12, p. 27485, § 178)
13-196-190  Standpipe systems – Where required.
   Standard inside standpipe systems, complying with the requirements of Chapter 15-16, shall be provided in all buildings exceeding 80 feet in height with the following exceptions:
   (a)   Institutional Units. In institutional units, standpipes shall be provided in all buildings more than four stories or 55 feet in height.
   (b)   Stage Blocks. In stage blocks, standpipes shall be provided on each side of the stage, on each tier of dressing rooms, and within 55 feet of all property rooms, store rooms or work rooms.
   (c)   Storage Structures. Standpipes shall not be required in grain elevators or similar storage structures, where such standpipes are ineffective owing to the type of structure and inaccessibility of hose connections.
      For the purpose of determining standpipe requirements, the height of a building shall be determined in accordance with the provisions of Section 13-48-020. Towers, steeples, tanks and similar structures not intended or used for human occupancy shall not be considered in determining the height.
   (d)   This section shall not apply to a building used as a business unit or storage unit, in existence prior to January 20, 1950, which is equipped throughout with an approved system of automatic sprinklers or is a fire resistive building of Type IA, IB or IC construction, provided that a standpipe system complying with Section 15-16-1190 is also provided in the building.
   (e)   In exhibition areas standpipes shall be provided regardless of the height of the building and standpipe locations shall provide complete coverage of the fire area with 100 foot hose lengths and 30 foot hose streams.
(Prior code § 78-18)
13-196-200  Standard fire alarm system requirements.
   An approved fire alarm system shall be provided as required in this section.
   (a)   A standard fire alarm system meeting the requirements of this chapter and Chapter 15-16 shall be provided in the following occupancies:
      (1)   Institutional: Buildings two stories or less in height with a floor area which does not exceed 8,000 square feet shall be equipped with a Class I system. Buildings over two stories in height or with a floor area exceeding 8,000 square feet shall be equipped with a Class II system;
      (2)   Type I or Type II schools: Buildings over one story in height shall be equipped with a Class I system;
      Any Type I school operating as or containing a day care center Class I, as defined in Section 13-4-010, shall comply with fire alarm system requirements applicable to Type III schools;
      (3)   Type III schools: Class I system;
      (3)   Type I or Type III schools: Class I system;
      (4)   Hotels: Buildings of Types II, III or IV construction 80 feet or less in height shall be equipped with a Class I system except where 25 or fewer persons sleep above the second floor;
      (5)   Single-room occupancy buildings: new and existing single-room occupancy buildings two stories or more in height, which are not equipped with a complete automatic sprinkler system, shall be equipped with a Class I fire alarm. The approved standard Class I control equipment may use microprocessor based program-controlled communication circuits when the control equipment is of a type tested and conforming to Underwriters Laboratories standard 864-1991 for the intended use. The stored program (software) installed figuration for such systems shall be incapable of change, except that a manufacturer's authorized technician may make changes for proper system operation when such changes are approved by the fire commissioner. Any changes, repairs or maintenance on such systems shall be performed only by or under the direction of a licensed supervising electrician.
      (6)   Dormitories: Buildings two stories or more in height; except those where 25 or fewer persons sleep above the second floor, shall be equipped with a Class I system;
      (7)   Intermediate care facilities for the developmentally disabled – 15 or fewer persons, same as institutional uses.
   (b)   Hotels: Buildings of Type 1 construction over four stories but not over 80 feet in height shall be equipped with an approved fire alarm system including smoke detectors, heat detectors and water flow alarm devices installed in accordance with NFPA 72-2013 and annunciated visually and audibly for each individual floor at a fire panel located near a main entrance to the building. A one-way voice communication system controlled from the fire panel location and meeting the requirements of Section 13-196-210(e)(2) shall be provided. Use of the one-way voice communication system in a fire emergency by other than department of fire personnel shall be prohibited.
      (1)   The fire alarm system shall be zoned horizontally based on the system design, but in no case shall there be less than one zone per floor.
      (2)   The fire alarm system shall be monitored by an Underwriters Laboratories Inc. listed Central Station service or shall be a Proprietary Protective Signaling System installed in accordance with NFPA 72-2013.
      (3)   A fire panel consisting of fire alarm controls, annunciator panel, and one-way voice communications system controls shall be provided in a location approved by the fire commissioner. Fire panels installed prior to the passage of this ordinance located on grade level in a readily accessible location shall be accepted.
      (4)   Plans for all systems to be installed shall be submitted to the fire commissioner for approval and systems used shall meet the approval of the fire commissioner.
   (c)   Notwithstanding any other provision of this Code to the contrary, the revisions to the requirements of this chapter and Chapter 15-16 contained in this amendatory ordinance shall apply to schools and day care centers in existence on the effective date of this amendatory ordinance beginning July 1, 1991.
   (d)   The requirements of subsection (a)(5) of this section shall be enforced against all single-room occupancy buildings effective June 30, 1995. All existing single-room occupancy buildings which will require installation of a Class I alarm system shall submit plans to the fire commissioner for approval of such system on or before January 1, 1995.
(Prior code § 78-19; Amend Coun. J. 9-8-86, p. 33588; Amend Coun. J. 6-27-90, p. 17613; Amend Coun. J. 5-4-94, p. 49750; Amend Coun. J. 5-9-12, p. 27485, § 179; Amend Coun. J. 5-18-16, p. 24131, § 48; Amend Coun. J. 9-6-17, p. 55278, Art. VII, § 15; Amend Coun. J. 3-28-18, p. 74459, Art. V, § 11)
13-196-203  Life safety data sheet – Required.
   (A)   No later than April 1, 2005, any owner of an existing building exceeding 80 feet in height above grade shall file with the fire department a life safety data sheet containing the following information about the building; (1) the name of the building owner of record, and, if applicable, the building manager; (2) the address of the building; (3) whether the building is residential or commercial or of mixed use; (4) if the building is residential or of mixed use, the number of dwelling units in the building; (5) the number of stories in the building; (6) whether the building is equipped with an automatic sprinkler system meeting any or all of the requirements of Chapter 15-16 of this Code, and identifying the areas so protected; and (7) whether the building is equipped with a standard inside standpipe system, a fire pump and a smokeproof tower.
   (B)   All information contained in the life safety data sheet shall be kept current. Any change in required information shall be reported by the building owner to the fire department within 14 days after the change. This subsection shall be enforceable against the building owner and against any subsequent owner.
   Any person who violates the requirements of this section shall be fined not less than $200.00 nor more than $500.00 for each offense. Each day that a violation continues shall constitute a separate and distinct offense.
(Added Coun. J. 12-15-04, p. 39962, § 1)
13-196-204  Voice communication systems in existing buildings.
   (A)   Subject to the exceptions listed below, no later than January 1, 2015, every existing building exceeding 80 feet in height above grade shall be equipped with the following: (i) a one-way voice communication system meeting the requirements of Section 13-76-050(b); and (ii) a two-way voice communication system meeting the requirements of Section 13-76-050(a); provided, however, that a telephone or other two-way communication system connected to an approved station, and installed pursuant to and in accordance with Option 2 of Section 13-196-084(a), shall be deemed to satisfy the requirements of item (ii) of this subsection.
   (B)   Neither a one-way nor a two-way voice communication system shall be required in the following buildings:
   Exception Number 1: Buildings that are classified as Class A-2, Multiple Dwellings, and are for non- transient residential use and are fully protected by automatic sprinklers.
   Exception Number 2: Institutional buildings and schools that have an approved standard fire alarm system as required by Section 15-16-110.
   (C)   A one-way voice communication system shall not be required in the following buildings:
   Exception Number 1: Non-transient residential buildings with an existing occupant notification system if a detailed description of the existing occupant notification system is submitted to and approved by the commissioner of buildings and the fire commissioner or by their designated representatives. In order to be considered for approval under this exception, and if approved under this exception, the existing occupant notification system shall meet the following criteria:
      (a)   the system must be in continuous use and must be tested on a monthly basis, or the system must have electronic supervision to indicate operational deficiencies in the system including, but not limited to, shorts, grounds and breaks in the circuit wiring; and
      (b)   the system must be audible throughout all required areas of the building, or must produce within all dwelling units a minimum sound level of 45 dBA within ten feet of any existing occupant notification system device; and
      (c)   the system must be able to transmit voice instructions without delay; and
      (d)   the system must be able to transmit voice instructions to all required areas or to all dwelling units at the same time; and
      (e)   the system must be available for fire department use from a central command location; and
      (f)   the system is subject to field testing; and
      (g)   replacement or modification of system components to meet the above criteria is limited to 50 percent of the reproduction cost of the existing occupant notification system.
   (D)   A two-way voice communication system shall not be required in the following buildings:
   Exception 1: Buildings that are classified as Class A-2, Multiple Dwellings, and are for non-transient residential use if the building does not exceed 15 stories in height and contains 60 or fewer dwelling units as defined in Section 13-4-010.
   (E)   For purposes of this section, “non-transient residential” means a residential use other than a hotel, motel, bed-and-breakfast establishment, dormitory, transitional shelter, emergency shelter or other temporary residential use.
   (F)   This section shall be enforceable against the building owner and against any subsequent owner.
(Added Coun. J. 12-15-04, p. 39962, § 2; Amend Coun. J. 11-18-09, p. 76565, § 1)
Loading...