Skip to code content (skip section selection)
Compare to:
Chicago Overview
Prior Chicago Building Code
BUILDING CODE AND RELATED EXCERPTS OF THE MUNICIPAL CODE OF CHICAGO
DIVISION 1 - ADMINISTRATION
DIVISION 2 - DEFINITIONS
DIVISION 3 - USE AND OCCUPANCY CLASSIFICATIONS
DIVISION 4 - SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY
DIVISION 5 - GENERAL BUILDING HEIGHTS AND AREAS
DIVISION 6 - TYPES OF CONSTRUCTION
DIVISION 7 - FIRE-RESISTANCE-RATED CONSTRUCTION
DIVISION 8 - INTERIOR FINISHES (NA)
DIVISION 9 - FIRE PROTECTION SYSTEMS
DIVISION 10 - MEANS OF EGRESS
DIVISION 11 - ACCESSIBILITY
DIVISION 12 - INTERIOR ENVIRONMENT
DIVISION 13 - ENERGY EFFICIENCY AND ENVIRONMENTAL PROTECTION
DIVISION 14 - EXTERIOR WALLS (NA)
DIVISION 15 - ROOF ASSEMBLIES AND ROOFTOP STRUCTURES (NA)
DIVISION 16 - STRUCTURAL DESIGN
DIVISION 17 - STRUCTURAL TESTS AND SPECIAL INSPECTIONS
DIVISION 18 - SOILS AND FOUNDATIONS
DIVISION 19 - CONCRETE
DIVISION 20 - ALUMINUM (NA)
DIVISION 21 - MASONRY
DIVISION 22 - STEEL
DIVISION 23 - WOOD
DIVISION 24 - GLASS AND GLAZING (NA)
DIVISION 25 - GYPSUM BOARD AND PLASTER (NA)
DIVISION 26 - PLASTIC (NA)
DIVISION 27 - ELECTRICAL
DIVISION 28 - MECHANICAL SYSTEMS
DIVISION 29 - PLUMBING SYSTEMS
DIVISION 30 - ELEVATORS AND CONVEYING SYSTEMS
DIVISION 31 - SPECIAL CONSTRUCTION (NA)
DIVISION 32 - ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
DIVISION 33 - SAFEGUARDS DURING CONSTRUCTION
DIVISION 34 - EXISTING STRUCTURES
Subdivision 3401 - General
CHAPTER 13-196 EXISTING BUILDINGS - MINIMUM REQUIREMENTS
13-196-010 Application.
13-196-020 Occupancy.
13-196-030 Structural stability.
13-196-031 Maintenance of exterior walls and enclosures - Definitions.
13-196-032 Maintenance of exterior walls and enclosures - Application.
13-196-033 Maintenance of exterior walls and enclosures - Critical examinations.
13-196-034 Maintenance of exterior walls and enclosures - Ongoing inspection and repair program.
13-196-035 Maintenance of exterior walls and enclosures - Reporting.
13-196-036 Maintenance of exterior walls - Retention of records at the building.
13-196-036.5 Reserved.
13-196-037 Maintenance of exterior walls and enclosures - Unsafe exterior walls and enclosures.
13-196-038 Rules and regulations.
13-196-038.5 Reserved.
13-196-039 Fines and penalties.
13-196-040 Floor loading.
13-196-050 Exit requirements.
13-196-060 Exits - Generally.
13-196-070 Exits - Types.
13-196-080 Passageways and exits to be unobstructed.
13-196-084 Stairwell re-entry in existing buildings.
13-196-085 Stairwell identification.
13-196-086 Area of rescue assistance identification.
13-196-090 Exit, stairway, fire escape and directional signs.
13-196-100 Smoke alarms - Where required.
13-196-110 Smoke alarms - Installation near sleeping rooms and in living levels.
13-196-120 Smoke alarms - Interior stairwell installation.
13-196-130 Smoke alarms - Standards.
13-196-140 Smoke alarms - Owner/tenant responsibilities.
13-196-150 Smoke alarms - Unlawful acts.
13-196-160 Reserved.
13-196-165 Carbon monoxide detectors.
13-196-170 Self-closing devices required for corridor doors.
13-196-180 Sprinkler systems - Where required.
13-196-190 Standpipe systems - Where required.
13-196-200 Standard fire alarm system requirements.
13-196-203 Life safety data sheet - Required.
13-196-204 Voice communication systems in existing buildings.
13-196-205 Automatic sprinkler system installation in existing high-rise buildings.
13-196-206 Life safety evaluation of existing high- rise buildings.
13-196-207 Materials and installation standards for retrofit fire protection systems.
13-196-208 Smokeproof towers in existing high- rise buildings - Fire shields.
13-196-209 High-rise buildings - Stairways - Doors - Frames.
13-196-210 High rise fire systems - Hotels.
13-196-220 Class II standard fire alarm systems.
13-196-230 Floor area and height.
13-196-240 Automatic fire detectors - Where required.
13-196-250 Permitted omission of sprinklers, heat and smoke detectors.
13-196-260 Fire extinguishers.
13-196-270 Elevator recall.
13-196-271 Continued operation.
13-196-280 Reserved.
13-196-290 Pre-ordinance hotels.
13-196-300 Institutional units.
13-196-310 Roominghouses.
13-196-320 Roominghouses - Sanitary facilities.
13-196-330 Roominghouses - Responsibility of operator.
13-196-340 Minimum requirements for residential buildings - General.
13-196-350 Residential buildings - Water closet.
13-196-360 Residential buildings - Lavatory.
13-196-370 Residential buildings - Bathtub or shower.
13-196-380 Residential buildings - Limitations on sharing sanitary facilities.
13-196-390 Residential buildings - Kitchen sink.
13-196-400 Residential buildings - Heating facilities.
13-196-410 Residential buildings - Heat to be furnished.
13-196-420 Residential buildings - Cold and hot water lines.
13-196-430 Residential buildings - Hot water to be furnished.
13-196-440 Gas-fired appliances.
13-196-450 Residential buildings - Hall and stairway lighting.
13-196-460 Residential buildings - Storage beneath stairways.
13-196-470 Residential buildings - Space, use and location - Applicability of provisions.
13-196-480 Residential buildings - Space requirements.
13-196-490 Residential buildings - Space requirements - Sleeping rooms.
13-196-500 Residential buildings - Access to water closets.
13-196-510 Residential buildings - Ceiling heights.
13-196-520 Residential buildings - Basement units.
13-196-530 Residential buildings - Foundations, exterior walls and roofs - Maintenance.
13-196-540 Residential buildings - Floors, interior walls and ceilings - Maintenance.
13-196-550 Residential buildings - Windows, doors and hatchways - Maintenance.
13-196-560 Residential buildings - Screens.
13-196-570 Residential buildings - Stairways and porches - Maintenance.
13-196-580 Residential buildings - Basements and cellars - Maintenance.
13-196-590 Residential buildings - Facilities, equipment, chimneys - Maintenance.
13-196-600 Residential buildings - Lot grading and drainage.
13-196-610 Residential buildings - Responsibilities of owners and occupants - General.
13-196-620 Residential buildings - Responsibilities of occupants.
13-196-630 Residential buildings - Responsibilities of owner or operator.
13-196-640 Residential buildings - Liability to city.
13-196-641 Application of certain sections.
13-196-650 Pre-ordinance conversion to existing buildings - Applicability.
13-196-660 Conversion of pre-ordinance buildings - Height limits.
13-196-670 Stairwells.
13-196-680 Corridors.
13-196-690 Dwelling separations.
13-196-700 Partitions.
13-196-710 Basement ceiling construction.
13-196-720 Heating plants.
13-196-730 Light and ventilation.
13-196-740 One additional dwelling unit over original allowed - Conditions.
13-196-750 Heat required.
13-196-760 Endangering health of employees.
Subdivision 3403 - Additions, Alterations or Repairs
DIVISION 35 - REFERENCED STANDARDS

You are viewing an archived code

Loading...
13-196-240  Automatic fire detectors – Where required.
   In every fire alarm system required in this Code, automatic fire detectors shall be installed as an integral part of a fire alarm system in rooms or portions of the building as follows:
   (a)   In all rooms where a flammable compressed gas or flammable liquid as described in Chapters 15-24 and 15-26, other than fuel oil for heating, is stored or used; also in shops and storerooms where combustible material is stored or handled.
   (b)   In every building used in part as an institutional building, school, hotel, or single-room occupancy, an automatic fire detector shall be installed in such portion or portions of the building used for purposes other than institutional, school, hotel, or single-room occupancy purposes, unless such institutional building, school, hotel, or single-room occupancy is separated from all other occupancies by a separation with a fire resistive value as specified in Section 13-56-280. Such automatic fire detectors shall be installed, spaced and located in accordance with the recommendations, based upon actual tests, prescribed by a nationally recognized testing laboratory acceptable to the fire prevention bureau.
   (c)   In every storeroom, maintenance shop, fan room, mechanical equipment room, laundry, linen room, janitor closet, kitchen and storage area.
   (d)   Fire alarm systems serving Type III schools, day care centers Class II, and those Type I schools operating as or containing a day care center Class I as defined in Section 13-4-010 shall include automatic detectors as follows:
      1.   Smoke detectors shall be installed at each floor level, including basements, of each interior stairwell up to and including one level above the level of the school or day care center, except in unoccupied attics.
      2.   Smoke detectors shall be installed in front of doors to stairwells from the school or day care center and at intervals of no less than 30 feet in all corridors within or serving the school or day care center.
      3.   Smoke detectors shall be located in all lounges, recreation areas and sleeping rooms.
      4.   Heat detectors shall be installed in boiler rooms, kitchens and combustible storage areas except where a sprinkler system with a flow alarm connected to the fire alarm system is installed in such rooms.
   (e)   In all two-story buildings occupied as open plan schools, (a story located below grade level shall be counted, if used for other than building service purposes), approved automatic fire detectors shall be installed throughout the building and be interconnected to the school fire alarm system.
   (f)   In hotel buildings over four stories, electrical equipment rooms, guest room corridors and elevator lobbies shall be equipped with automatic smoke detectors installed in accordance with NFPA 72-2013.
   (g)   In single-room occupancy buildings, automatic heat detectors shall be installed in each single- room occupancy unit, in public corridors, and at each floor level in every interior stairwell. In single-room occupancy buildings, smoke alarms required by Section 13-196-100 need not be connected to the fire alarm system, but shall be permanently wired to the electrical wiring system of the building.
(Prior code § 78-22; Amend Coun. J. 9-8-86, p. 33588; Amend Coun. J. 6-27-90, p. 17613; Amend Coun. J. 5-4-94, 49750; Amend Coun. J. 5-9-12, p. 27485, § 180; Amend Coun. J. 11-9-16, p. 36266, § 26; Amend Coun. J. 9-6-17, p. 55278, Art. VI, § 31)
13-196-250  Permitted omission of sprinklers, heat and smoke detectors.
   No automatic heat detector shall be required in any room or portion of a building which is equipped with an approved installation of automatic sprinklers and provided with a water flow alarm which is connected to the fire alarm system. No automatic smoke detector shall be required in guest room corridors nor elevator lobbies of hotel buildings equipped with an approved system of automatic sprinklers. Sprinklers may be omitted in guest room closets not over 24 square feet in area. Other areas not sprinklered, because of unreasonable hardship or as permitted by Section 15-16-350 of the Code, shall be protected by approved smoke detectors or other fire detection measures approved by the fire commissioner. Detectors shall not be required in guest room bathrooms. No automatic smoke detector shall be required in guest room corridors nor elevator to the lobbies of existing buildings having automatic sprinkler systems installed prior to the passage of this ordinance on guest room floors except that sprinkler systems installed prior to the passage of this ordinance on guest room floors except that sprinkler systems may be omitted in guest room bathrooms over 55 square feet in area with noncombustible plumbing fixtures and with walls and ceilings surfaced with noncombustible materials.
(Prior code § 78-23; Amend Coun. J. 9-8-86, p. 33588; Amend Coun. J. 5-18-16, p. 24131, § 54)
13-196-260  Fire extinguishers.
   Standard fire extinguishers shall be provided in accordance with the provisions of Sections 15-16-620 through and including 15-16-680 of this Code.
(Prior code § 78-24)
13-196-270  Elevator recall.
   All existing buildings shall comply with the requirements of Section 14C-4-3.11.3.
(Added Coun. J. 6-14-95, p. 2820; Amend Coun. J. 1-10-01, p. 50236, § 2; Amend Coun. J. 3-28-18, p. 74459, Art. II, § 19)
13-196-271  Continued operation.
   In buildings equipped with passenger elevators, not less than one passenger elevator shall be maintained in operation at all times when the building is occupied.
   Exception: Buildings equipped with only one passenger elevator shall be permitted to have the elevator temporarily out of service for testing or servicing.
(Added Coun. J. 3-28-18, p. 74459, Art. II, § 20)
13-196-280  Reserved.
Editor's note – Coun. J. 1-10-01, p. 50236, § 1, repealed § 13-196-280, which pertained to elevator safety device test.
13-196-290  Pre-ordinance hotels.
   Every pre-ordinance hotel (built before July 7, 1957) more than two stories and basement in height, having sleeping accommodations for more than 25 persons above the second story, and every pre-ordinance hotel of any capacity more than four stories and basement in height, shall comply with the requirements of Section 15-8-120 pertaining to the protection of stairs, shafts and vertical openings, except as follows:
   (a)   Enclosing walls and partitions may be of construction providing fire resistance of not less than one hour.
   (b)   Doors required for protection of openings in enclosures may be Class C fire doors of combustible material faced on both sides with materials not less fire resistive than sheet steel 18 gauge in thickness. Openings, if any, shall be glazed with wire glass and shall not exceed 144 square inches in area, except that existing openings not exceeding 1,296 square inches in area may be permitted.
   (c)   Where the top or bottom riser in a stairwell is so located that the vertical enclosures therein required will not be practical to erect without unreasonable hardship, a horizontal cutoff there shall be not more than three openings to dwelling units or other nonpublic spaces on each floor, and such dwelling units or nonpublic spaces shall be separated from the corridor by partitions providing fire resistance of not less than one hour with all openings protected with self-closing Class C fire doors.
(Prior code § 78-27)
Loading...