905.3 Vent connection to drainage system.
Every dry vent connecting to a horizontal drain shall connect above the centerline of the horizontal drain pipe.
905.4 Reserved.
905.5 Height above fixtures.
A connection between a vent pipe and a vent stack or stack vent shall be made at not less than 6 inches (152 mm) above the flood level rim of the highest fixture served by the vent. Horizontal vent pipes forming branch vents, relief vents or loop vents shall be located not less than 6 inches (152 mm) above the flood level rim of the highest fixture served.
905.6 Vent for future fixtures.
Where the drainage piping has been roughed-in for future fixtures, a rough-in connection for a vent shall be installed. The vent size shall be not less than one-half the diameter of the rough-in drain to be served. The vent rough-in shall connect to the vent system, or shall be vented by other means as provided for in this chapter. The connection shall be identified to indicate that it is a vent.
906.1 Size of stack vents and vent stacks.
The minimum required diameter of stack vents and vent stacks shall be determined from the developed length and the total of drainage fixture units connected thereto in accordance with Table 906.1, but in no case shall the diameter be less than one-half the diameter of the drain served or less than 1 1/4 inches (32 mm).
Diameter of Soil or Waste Stack (inches) | Total Fixture Units Being Vented (dfu) | Maximum Developed Length of Vent (feet) a Diameter of Vent (inches) |
Diameter of Soil or Waste Stack (inches) | Total Fixture Units Being Vented (dfu) | Maximum Developed Length of Vent (feet) a Diameter of Vent (inches) | ||||||||||
1 1/4 | 1 1/2 | 2 | 2 1/2 | 3 | 4 | 5 | 6 | 8 | 10 | 12
| ||
1 1/4 | 2 | 30 | — | — | — | — | — | — | — | — | — | |
1 1/2 | 8 | 50 | 150 | |||||||||
1 1/2 | 10 | 30 | 100 | |||||||||
2 | 12 | 75 | 200 | — | — | — | — | — | — | — | ||
2 | 20 | 30 | 50 | 150 | ||||||||
2 1/2 | 42 | 26 | 30 | 100 | 300 | |||||||
3 | 10 | — | 42 | 150 | 360 | 1,040 | — | — | — | — | — | — |
3 | 21 | 32 | 110 | 270 | 810 | |||||||
3 | 53 | 27 | 94 | 230 | 680 | |||||||
3 | 102 | — | 25 | 86 | 210 | 620 | — | — | — | — | — | |
4 | 43 | 35 | 85 | 250 | 980 | |||||||
4 | 140 | 27 | 65 | 200 | 750 | |||||||
4 | 320 | — | — | 23 | 55 | 170 | 640 | — | — | — | — | |
4 | 540 | 21 | 50 | 150 | 580 | |||||||
5 | 190 | 28 | 82 | 320 | 990 | |||||||
5 | 490 | — | — | — | 21 | 63 | 250 | 760 | — | — | — | — |
5 | 940 | 18 | 53 | 210 | 670 | |||||||
5 | 1,400 | 16 | 49 | 190 | 590 | |||||||
6 | 500 | — | — | — | — | 33 | 130 | 400 | 1,000 | — | — | — |
6 | 1,100 | 26 | 100 | 310 | 780 | |||||||
6 | 2,000 | 22 | 84 | 260 | 660 | |||||||
6 | 2,900 | — | — | — | — | 20 | 77 | 240 | 600 | — | — | |
8 | 1,800 | 31 | 95 | 240 | 940 | |||||||
8 | 3,400 | 24 | 73 | 190 | 729 | |||||||
8 | 5,600 | — | — | — | — | — | 20 | 62 | 160 | 610 | — | |
8 | 7,600 | 18 | 56 | 140 | 560 | |||||||
10 | 4,000 | 31 | 78 | 310 | 960 | |||||||
10 | 7,200 | — | — | — | — | — | — | 24 | 60 | 240 | 740 | — |
10 | 11,000 | 20 | 51 | 200 | 630 | |||||||
10 | 15,000 | 18 | 46 | 180 | 571 | |||||||
12 | 7,300 | — | — | — | — | — | — | — | 31 | 120 | 380 | 940 |
12 | 13,000 | 24 | 94 | 300 | 720 | |||||||
12 | 20,000 | 20 | 79 | 250 | 610 | |||||||
12 | 26,000 | — | — | — | — | — | — | — | 18 | 72 | 230 | 500 |
15 | 15,000 | 40 | 130 | 310 | ||||||||
15 | 25,000 | 31 | 96 | 240 | ||||||||
15 | 38,000 | — | — | — | — | — | — | — | — | 26 | 81 | 200 |
15 | 50,000 | 24 | 74 | 180 | ||||||||
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
a. The developed length shall be measured from the vent connection to the open air.