906.1 Size of stack vents and vent stacks.
The minimum required diameter of stack vents and vent stacks shall be determined from the developed length and the total of drainage fixture units connected thereto in accordance with Table 906.1, but in no case shall the diameter be less than one-half the diameter of the drain served or less than 1 1/4 inches (32 mm).
Diameter of Soil or Waste Stack (inches) | Total Fixture Units Being Vented (dfu) | Maximum Developed Length of Vent (feet) a Diameter of Vent (inches) |
Diameter of Soil or Waste Stack (inches) | Total Fixture Units Being Vented (dfu) | Maximum Developed Length of Vent (feet) a Diameter of Vent (inches) | ||||||||||
1 1/4 | 1 1/2 | 2 | 2 1/2 | 3 | 4 | 5 | 6 | 8 | 10 | 12
| ||
1 1/4 | 2 | 30 | — | — | — | — | — | — | — | — | — | |
1 1/2 | 8 | 50 | 150 | |||||||||
1 1/2 | 10 | 30 | 100 | |||||||||
2 | 12 | 75 | 200 | — | — | — | — | — | — | — | ||
2 | 20 | 30 | 50 | 150 | ||||||||
2 1/2 | 42 | 26 | 30 | 100 | 300 | |||||||
3 | 10 | — | 42 | 150 | 360 | 1,040 | — | — | — | — | — | — |
3 | 21 | 32 | 110 | 270 | 810 | |||||||
3 | 53 | 27 | 94 | 230 | 680 | |||||||
3 | 102 | — | 25 | 86 | 210 | 620 | — | — | — | — | — | |
4 | 43 | 35 | 85 | 250 | 980 | |||||||
4 | 140 | 27 | 65 | 200 | 750 | |||||||
4 | 320 | — | — | 23 | 55 | 170 | 640 | — | — | — | — | |
4 | 540 | 21 | 50 | 150 | 580 | |||||||
5 | 190 | 28 | 82 | 320 | 990 | |||||||
5 | 490 | — | — | — | 21 | 63 | 250 | 760 | — | — | — | — |
5 | 940 | 18 | 53 | 210 | 670 | |||||||
5 | 1,400 | 16 | 49 | 190 | 590 | |||||||
6 | 500 | — | — | — | — | 33 | 130 | 400 | 1,000 | — | — | — |
6 | 1,100 | 26 | 100 | 310 | 780 | |||||||
6 | 2,000 | 22 | 84 | 260 | 660 | |||||||
6 | 2,900 | — | — | — | — | 20 | 77 | 240 | 600 | — | — | |
8 | 1,800 | 31 | 95 | 240 | 940 | |||||||
8 | 3,400 | 24 | 73 | 190 | 729 | |||||||
8 | 5,600 | — | — | — | — | — | 20 | 62 | 160 | 610 | — | |
8 | 7,600 | 18 | 56 | 140 | 560 | |||||||
10 | 4,000 | 31 | 78 | 310 | 960 | |||||||
10 | 7,200 | — | — | — | — | — | — | 24 | 60 | 240 | 740 | — |
10 | 11,000 | 20 | 51 | 200 | 630 | |||||||
10 | 15,000 | 18 | 46 | 180 | 571 | |||||||
12 | 7,300 | — | — | — | — | — | — | — | 31 | 120 | 380 | 940 |
12 | 13,000 | 24 | 94 | 300 | 720 | |||||||
12 | 20,000 | 20 | 79 | 250 | 610 | |||||||
12 | 26,000 | — | — | — | — | — | — | — | 18 | 72 | 230 | 500 |
15 | 15,000 | 40 | 130 | 310 | ||||||||
15 | 25,000 | 31 | 96 | 240 | ||||||||
15 | 38,000 | — | — | — | — | — | — | — | — | 26 | 81 | 200 |
15 | 50,000 | 24 | 74 | 180 | ||||||||
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
a. The developed length shall be measured from the vent connection to the open air.
906.2 Vents other than stack vents or vent stacks.
The diameter of individual vents, branch vents, circuit vents and relief vents shall be at least one-half the required diameter of the drain served. The required size of the drain shall be determined in accordance with Table 710.1(2). Vent pipes shall not be less than 1 1/4 inches (32 mm) in diameter. Vents shall be sized in accordance with Table 906.1 utilizing the drainage fixture units and the corresponding developed length. Relief vents for soil and waste stacks in buildings having more than 10 branch intervals shall be sized in accordance with Section 908.2.