608.8.2.1 Color.
The color of the pipe identification shall be discernable and consistent throughout the building. The color purple shall be used to identify nonpotable water distribution systems.
608.8.2.2 Lettering size.
Pipe Diameter (inches) | Length Background Color Field (inches) | Size of Letters (inches) |
3/4 to 1 1/4 | 8 | 0.5 |
1 1/2 to 2 | 8 | 0.75 |
2 1/2 to 6 | 12 | 1.25 |
8 to 10 | 24 | 2.5 |
over 10 | 32 | 3.5 |
For SI: 1 inch = 25.4 mm.
608.8.2.3 Identification tape.
Where used, identification tape shall be at least 3 inches (76 mm) wide and have white or black lettering on a purple field stating "CAUTION: NONPOTABLE WATER – DO NOT DRINK." Identification tape shall be installed on top of nonpotable water distribution pipes, fastened at least every 10 feet (3048 mm) to each pipe length and run continuously the entire length of the pipe.