608.15 Protection of potable water outlets.
All potable water openings and outlets shall be protected against backflow in accordance with Section 608.15.1, 608.15.2, 608.15.3, 608.15.4, 608.15.4.1 or 608.15.4.2.
608.15.1 Protection by air gap.
Openings and outlets shall be protected by an air gap between the opening and the fixture flood level rim as specified in Table 608.15.1. Openings and outlets equipped for hose connection shall be protected by means other than an air gap.
Fixture | Minimum Air Gap | |
Away from a Wall a (inches) | Close to a Wall (inches) | |
Lavatories and other fixtures with effective openings not greater than 1/2 inch in diameter | 1 | 1 1/2 |
Sinks, laundry trays, gooseneck back faucets and other fixtures with effective openings not greater than 3/4 inch in diameter | 1 1/2 | 2 1/2 |
Over-rim bath fillers and other fixtures with effective openings not greater than 1 inch in diameter | 2 | 3 |
Drinking water fountains, single orifice not greater than 7/16 inch in diameter or multiple orifices with a total area of 0.150 square inch (area of circle 7/16 inch in diameter) | 1 | 1 1/2 |
Effective openings greater than 1 inch | Two times the diameter of the effective opening | Three times the diameter of the effective opening |
For SI: 1 inch = 25.4 mm, 1 square inch = 645 mm2.
a. Applicable where walls or obstructions are spaced from the nearest inside-edge of the spout opening a distance greater than three times the diameter of the effective opening for a single wall, or a distance greater than four times the diameter of the effective opening for two intersecting walls.
608.15.2 Protection by reduced pressure principle backflow prevention assembly.
Openings and outlets shall be protected by a reduced pressure principle backflow prevention assembly or a reduced pressure principle fire protection backflow prevention assembly on potable water supplies.