604.6 Variable street pressures.
Where street water main pressures fluctuate, the building water distribution system shall be designed for the minimum pressure available.
604.7 Inadequate water pressure.
Wherever water pressure from the street main or other source of supply is insufficient to provide flow pressures at fixture outlets as required under Table 604.3, a water pressure booster system conforming to Section 606.5 shall be installed on the building water supply system.
604.8 Water pressure-reducing valve or regulator.
Where water pressure within a building exceeds 85 psi (586 kPa) static, an approved valve conforming to ASSE 1003 or CSA B356 with strainer shall be installed to reduce the pressure in the building water distribution piping to not greater than 85 psi (586 kPa) static.
Exception: Service lines to sill cocks and outside hydrants, and main supply risers where pressure from the mains is reduced to 85 psi (586 kPa) or less at individual fixtures.