5003.2.4 Installation of tanks.
Installation of tanks shall be in accordance with FC 5003.2.4.1 through 5003.2.4.3 and with the regulations of the New York State Department of Environmental Conservation as set forth in 6 NYCRR Sections 599 and 613.
5003.2.4.1 Underground tanks.
Underground tanks used for the storage of liquid hazardous materials shall be provided with secondary containment.
5003.2.4.2 Aboveground tanks.
Aboveground stationary tanks used for the storage of liquid hazardous materials shall be located and protected in compliance with the requirements for outdoor storage of the particular material involved.
5003.2.4.2.1 Marking.
Aboveground stationary tanks shall be marked as required by FC 5003.5.
5003.2.4.3 Flood hazard.
Hazardous materials storage tanks located in areas of special flood hazard or on the premises of Group I-2 occupancies that are hospitals located in shaded X-Zones (as defined in Section G201.2 of the Building Code) shall comply with Section G307.5 of Appendix G of the Building Code.
5003.2.5 Empty containers and tanks.
Empty containers and tanks previously used for the storage of hazardous materials shall be free from residual material and vapor in compliance with the requirements of DOTn, the Resource Conservation and Recovery Act (RCRA) or other governmental agencies having jurisdiction, or shall be stored, handled and used in compliance with the requirements of this code.