Every existing building must be equipped with standpipes in each fire area containing an exhibition area, spaced to provide complete coverage with 100 foot (30.5 m) hose lengths and 30 foot (9.1 m) hose streams.
Exception: Buildings that do not contain more than 5,000 square feet (465 m2) of floor area, in aggregate, used as an exhibition area.
A fire alarm system must be installed in existing buildings in accordance with Sections 14X-5-504.6.1 through 14X-5-504.6.7 and provide occupant notification in accordance with the Chicago Building Code unless other requirements are provided by other sections of this code or the Chicago Fire Prevention Code.
Exception: Occupancies with an existing, permitted fire alarm system.