Skip to code content (skip section selection)
Compare to:
Chicago Overview
Municipal Code of Chicago
MUNICIPAL CODE OF CHICAGO
TITLE 1 GENERAL PROVISIONS
TITLE 2 CITY GOVERNMENT AND ADMINISTRATION
TITLE 3 REVENUE AND FINANCE
TITLE 4 BUSINESSES, OCCUPATIONS AND CONSUMER PROTECTION
TITLE 5 HOUSING AND ECONOMIC DEVELOPMENT
TITLE 6 HUMAN RIGHTS*
TITLE 7 HEALTH AND SAFETY
TITLE 8 OFFENSES AFFECTING PUBLIC PEACE, MORALS AND WELFARE
TITLE 9 VEHICLES, TRAFFIC AND RAIL TRANSPORTATION
TITLE 10 STREETS, PUBLIC WAYS, PARKS, AIRPORTS AND HARBORS
TITLE 11 UTILITIES AND ENVIRONMENTAL PROTECTION
TITLE 12 RESERVED
TITLE 13 BUILDINGS AND CONSTRUCTION
TITLE 14 RESERVED*
TITLE 14A ADMINISTRATIVE PROVISIONS OF THE CHICAGO CONSTRUCTION CODES*
TITLE 14B BUILDING CODE*
TITLE 14C CONVEYANCE DEVICE CODE*
TITLE 14E ELECTRICAL CODE*
TITLE 14F FIRE PREVENTION CODE*
TITLE 14G FUEL GAS CODE*
TITLE 14M MECHANICAL CODE*
TITLE 14N 2022 ENERGY TRANSFORMATION CODE*
TITLE 14P PLUMBING CODE*
TITLE 14R BUILDING REHABILITATION CODE*
TITLE 14X MINIMUM REQUIREMENTS FOR EXISTING BUILDINGS*
CHAPTER 14X-1 SCOPE AND PURPOSE
CHAPTER 14X-2 DEFINITIONS
CHAPTER 14X-3 PROPERTY MAINTENANCE
CHAPTER 14X-4 RESIDENTIAL OCCUPANCIES
CHAPTER 14X-5 FIRE SAFETY REQUIREMENTS
CHAPTER 14X-6 LIGHT AND VENTILATION
CHAPTER 14X-7 ELECTRICAL REQUIREMENTS
CHAPTER 14X-8 HEATING, COOLING, AND MECHANICAL SYSTEMS
CHAPTER 14X-9 PLUMBING SYSTEMS AND FIXTURES
CHAPTER 14X-10 ELEVATORS AND OTHER CONVEYANCE DEVICES
CHAPTER 14X-11 RESERVED
CHAPTER 14X-12 VACANT BUILDINGS, STRUCTURES, AND COMMERCIAL STOREFRONTS*
CHAPTER 14X-20 REFERENCED STANDARDS
TITLE 15 FIRE PREVENTION
TITLE 16 LAND USE
TITLE 17 CHICAGO ZONING ORDINANCE
TITLE 18 BUILDING INFRASTRUCTURE
APPENDIX TO THE MUNICIPAL CODE OF CHICAGO (RESERVED)*
TABLES
Chicago Zoning Ordinance and Land Use Ordinance
Loading...
14X-5-504.4 Standpipes.
Existing structures must be equipped with standpipes installed in accordance with Section 905 of the Chicago Building Code where required in Sections 14X-5-504.4.1 through 14X-5-504.4.4. The fire code official is authorized to approve the installation of manual dry or manual wet standpipe systems to achieve compliance with this section.
Exceptions:
1.   Occupancies with existing, permitted standpipes.
2.   Standpipes are not required in grain elevators or similar storage structures where standpipes would be ineffective due to the type of structure and inaccessibility of hose connections.
14X-5-504.4.1 Group A-1.
Every existing building containing a Group A-1 occupancy must have standpipes provided on each side of the stage block. In fire areas not equipped with an automatic sprinkler system, standpipes must also be provided on each tier of dressing rooms and within 50 feet (15.2 m) of all property rooms, store rooms, or work rooms.
14X-5-504.4.2 Group A, exhibition areas.
Every existing building must be equipped with standpipes in each fire area containing an exhibition area, spaced to provide complete coverage with 100 foot (30.5 m) hose lengths and 30 foot (9.1 m) hose streams.
Exception: Buildings that do not contain more than 5,000 square feet (465 m2) of floor area, in aggregate, used as an exhibition area.
14X-5-504.4.3 Group I.
Every existing building containing a Group I occupancy which exceeds 55 feet (16.8 m) in building height or contains more than 4 stories above grade plane must be equipped with standpipes.
(Amend Coun. J. 2-19-20, p. 14473, Art. V, § 24)
14X-5-504.4.4 High-rise buildings.
Every high-rise building must be equipped with standpipes.
14X-5-504.5 Portable fire extinguishers.
Portable fire extinguishers must be provided in existing buildings in accordance with Section 906 of the Chicago Building Code. Portable fire extinguishers must be maintained in accordance with the Chicago Fire Prevention Code.