Skip to code content (skip section selection)
Compare to:
Chicago Overview
Municipal Code of Chicago
MUNICIPAL CODE OF CHICAGO
TITLE 1 GENERAL PROVISIONS
TITLE 2 CITY GOVERNMENT AND ADMINISTRATION
TITLE 3 REVENUE AND FINANCE
TITLE 4 BUSINESSES, OCCUPATIONS AND CONSUMER PROTECTION
TITLE 5 HOUSING AND ECONOMIC DEVELOPMENT
TITLE 6 HUMAN RIGHTS*
TITLE 7 HEALTH AND SAFETY
TITLE 8 OFFENSES AFFECTING PUBLIC PEACE, MORALS AND WELFARE
TITLE 9 VEHICLES, TRAFFIC AND RAIL TRANSPORTATION
TITLE 10 STREETS, PUBLIC WAYS, PARKS, AIRPORTS AND HARBORS
TITLE 11 UTILITIES AND ENVIRONMENTAL PROTECTION
TITLE 12 RESERVED
TITLE 13 BUILDINGS AND CONSTRUCTION
TITLE 14 RESERVED*
TITLE 14A ADMINISTRATIVE PROVISIONS OF THE CHICAGO CONSTRUCTION CODES*
TITLE 14B BUILDING CODE*
TITLE 14C CONVEYANCE DEVICE CODE*
TITLE 14E ELECTRICAL CODE*
TITLE 14F FIRE PREVENTION CODE*
TITLE 14G FUEL GAS CODE*
TITLE 14M MECHANICAL CODE*
TITLE 14N 2022 ENERGY TRANSFORMATION CODE*
TITLE 14P PLUMBING CODE*
TITLE 14R BUILDING REHABILITATION CODE*
TITLE 14X MINIMUM REQUIREMENTS FOR EXISTING BUILDINGS*
CHAPTER 14X-1 SCOPE AND PURPOSE
CHAPTER 14X-2 DEFINITIONS
CHAPTER 14X-3 PROPERTY MAINTENANCE
CHAPTER 14X-4 RESIDENTIAL OCCUPANCIES
CHAPTER 14X-5 FIRE SAFETY REQUIREMENTS
14X-5-501 GENERAL.
14X-5-502 FIRE AND SMOKE PROTECTION FEATURES.
14X-5-503 RESERVED.
14X-5-504 FIRE PROTECTION AND LIFE SAFETY SYSTEMS.
14X-5-505 MEANS OF EGRESS.
14X-5-506 LIFE SAFETY COMPLIANCE PLAN.
CHAPTER 14X-6 LIGHT AND VENTILATION
CHAPTER 14X-7 ELECTRICAL REQUIREMENTS
CHAPTER 14X-8 HEATING, COOLING, AND MECHANICAL SYSTEMS
CHAPTER 14X-9 PLUMBING SYSTEMS AND FIXTURES
CHAPTER 14X-10 ELEVATORS AND OTHER CONVEYANCE DEVICES
CHAPTER 14X-11 RESERVED
CHAPTER 14X-12 VACANT BUILDINGS, STRUCTURES, AND COMMERCIAL STOREFRONTS*
CHAPTER 14X-20 REFERENCED STANDARDS
TITLE 15 FIRE PREVENTION
TITLE 16 LAND USE
TITLE 17 CHICAGO ZONING ORDINANCE
TITLE 18 BUILDING INFRASTRUCTURE
APPENDIX TO THE MUNICIPAL CODE OF CHICAGO (RESERVED)*
TABLES
Chicago Zoning Ordinance and Land Use Ordinance
Loading...
14X-5-504.2.8 Pyroxylin plastics.
An automatic sprinkler system must be provided throughout existing buildings where cellulose nitrate film or pyroxylin plastics are manufactured, stored, or handled in quantities exceeding 100 pounds (45 kg). Vaults located within buildings for the storage of raw pyroxylin must be protected with an automatic sprinkler system capable of discharging 1.66 gallons per minute per square foot (68 L/min/m2) over the area of the vault.
14X-5-504.2.9 High-rise buildings.
An automatic sprinkler system must be provided throughout high-rise buildings.
Exceptions:
1.   Parking facilities complying with Section 406 of the Chicago Building Code.
2.   Open-air portions of a Group A-5 occupancy.
3.   A building of Group R-2 occupancy, together with any accessory occupancies complying with Section 508.2 of the Chicago Building Code and any attached parking garage that is used exclusively by the building’s non-transient residential occupants and their guests or by persons who, pursuant to a written lease agreement, rent a parking space in time increments of at least one month.
4.   The following portions of a mixed-occupancy building where separated from other occupancies by construction having a fire-resistance rating of not less than 2 hours:
4.1.   Any portion classified as Group R-2 occupancy.
4.2.   Any accessory occupancy connected to the Group R-2 occupancy and complying with Section 508.2 of the Chicago Building Code.
4.3.   A parking garage that is used exclusively by the building’s non-transient residential occupants and their guests or by persons who, pursuant to a written lease agreement, rent a parking space in time increments of at least one month.
4.4.   In buildings of Type I construction, non-residential occupancies located not more than 80 feet (24.4 m) above grade that are separated in accordance with Section 508.4 of the Chicago Building Code and that cumulatively do not exceed 10% of the floor area of the Group R-2 occupancy in the building.
5.   A Chicago Landmark, unless the building is required to be equipped with an automatic sprinkler system by another provision of the Municipal Code.
6.   A building color-coded red or orange in the Chicago Historic Resources Survey, published in 1996, unless the building is required to be equipped with an automatic sprinkler system by another provision of the Municipal Code.
14X-5-504.3 Automatic fire-extinguishing systems.
An automatic sprinkler system, installed in accordance with Section 903 of the Chicago Building Code, or an alternative automatic fire-extinguishing system, installed in accordance with Section 904 of the Chicago Building Code, must be provided in existing structures in accordance with Sections 14X-5-504.3.1 through 14X-5-504.3.3.
Exception: Occupancies with an existing, permitted automatic fire-extinguishing system.
14X-5-504.3.1 Public utility structures.
Every existing structure that is owned or operated by any person whose primary business is the generation or transmission of electrical power and that houses one or more electrical generators, electrical transformers, or switching equipment for a service area beyond the structure in which the equipment is located must be equipped throughout with an automatic fire-extinguishing system.
14X-5-504.3.2 Telecommunication equipment areas.
Every fire area within an existing structure containing a telecommunication equipment area that exceeds 150 square feet (13.93 m2) must be equipped with an automatic fire-extinguishing system.
14X-5-504.3.3 Telephone exchanges.
Every existing structure which is used as a telephone exchange must be equipped throughout with an automatic fire-extinguishing system.
14X-5-504.4 Standpipes.
Existing structures must be equipped with standpipes installed in accordance with Section 905 of the Chicago Building Code where required in Sections 14X-5-504.4.1 through 14X-5-504.4.4. The fire code official is authorized to approve the installation of manual dry or manual wet standpipe systems to achieve compliance with this section.
Exceptions:
1.   Occupancies with existing, permitted standpipes.
2.   Standpipes are not required in grain elevators or similar storage structures where standpipes would be ineffective due to the type of structure and inaccessibility of hose connections.
14X-5-504.4.1 Group A-1.
Every existing building containing a Group A-1 occupancy must have standpipes provided on each side of the stage block. In fire areas not equipped with an automatic sprinkler system, standpipes must also be provided on each tier of dressing rooms and within 50 feet (15.2 m) of all property rooms, store rooms, or work rooms.