Every existing building or portion of an existing building used as an exhibition area must be equipped with an automatic sprinkler system. Every area used for storage of combustible materials in a building containing an exhibition area must be equipped with an automatic sprinkler system.
Exception: Buildings that do not contain more than 5,000 square feet (465 m2) of floor area, in aggregate, used as an exhibition area.
Every existing building of Type III, IV, or V construction and with two or more stories above grade plane which is used entirely for education above the 12th grade, adult education, or as a commercial or vocational school for more than 100 persons must be equipped throughout with an automatic sprinkler system.
Every existing building of Type III, IV, or V construction and with two or more stories above grade plane which contains a fire area of Group I-1, condition 2, or Group I-2 occupancy used as a hospital, psychiatric hospital, assisted living facility, or foster care facility must be equipped throughout with an automatic sprinkler system.
Every existing building containing a Group I-2 nursing home must be equipped throughout with an automatic sprinkler system.
An automatic sprinkler system must be provided throughout existing buildings where cellulose nitrate film or pyroxylin plastics are manufactured, stored, or handled in quantities exceeding 100 pounds (45 kg). Vaults located within buildings for the storage of raw pyroxylin must be protected with an automatic sprinkler system capable of discharging 1.66 gallons per minute per square foot (68 L/min/m2) over the area of the vault.