The provisions of Article 515 of NFPA 70 are adopted by reference with the following modifications:
1. Revise subsection 515.7(A) to read:
"Fixed Wiring. All fixed wiring above Class I locations shall be in metal raceways, or Type MI, Type TC, or Type PLTC and Type PLTC-ER cable in accordance with the provisions of Article 725, or Type ITC and Type ITC-ER cable as permitted in 727.4. The cable shall be terminated with listed fittings."
2. [Reserved.]
3. Delete subsection 515.8(C).
(Amend Coun. J. 10-7-20, p. 21791, Art. III, § 7)