The provisions of Article 506 of NFPA 70 are adopted by reference with the following modifications.
1. Revise subsection 506.15(A) by deleting items (3) and (4).
2. Revise subsection 506.15(C) item (3) to read:
"Type MI cable with listed termination fittings."
3. Revise subsection 506.15(C) by deleting items (4), (5), and (6).
The provisions of Article 511 of NFPA 70 are adopted by reference with the following modifications:
1. Revise subsection 511.7(A)(1) to read:
"Fixed Wiring Above Class I Locations. All fixed wiring above Class I locations shall be in metal raceways, flexible metal conduit, liquidtight flexible metal conduit, or shall be Type MI, or PLTC cable in accordance with Article 725, or Type TC cable or Type ITC cable in accordance with Article 727."
(Amend Coun. J. 10-7-20, p. 21791, Art. III, ยง 5)