Loading...
Auxiliary Business Use. Every hazardous use unit required in Chapters 15-16, 15-20, 15-24, and 15-26 to be isolated from every other building or structure shall be located in a building used for no purpose, other than that of the purposes of such a hazardous use unit; provided, however, that any such building may have an auxiliary office designed, intended and used for the regular occupancy of not more than three persons.
Adjoining Other Occupancies. The following hazardous use units shall be permitted to adjoin a building having the same occupancy, or a building having one or more other occupancies:
Corrosive liquid storage buildings;
Cereal, feed, flour, grist and starch mills;
Dry cleaning building, subject to the provisions of Section 15-24-920 of this Code;
Fume or flammable compressed gas buildings, subject to the provisions of Chapter 15-26 of this Code;
Highly flammable material storage buildings;
Smoke houses.
Any such building except a dry cleaning building may have an auxiliary office, designed, intended or used for the regular occupancy of not more than six persons.
Hazardous Use Units Prohibited. A hazardous use unit shall not be permitted in any building used for any other occupancy except as provided by Section 13-56-280 of this Code.
(Prior code § 60-8; Amend Coun. J. 6-14-95, p. 2841; Amend Coun. J. 11-9-16, p. 36266, § 24)
ARTICLE III. ROOMS AND FLOOR AREAS (13-112-120 et seq.)
None of the following herein described hazardous use units:
Asphalt, tar, pitch, resin or paraffin heating room;
Corrosive liquid storage room;
Dip tanks having a capacity or liquid surface area in excess of the following:
Capacity | Liquid Surface Area | |
Class I | 10 gallons | 4 square feet |
Class II | 60 gallons | 10 square feet |
Class III | 125 gallons | 15 square feet |
Drying room for any article or material which will give off explosive or flammable vapors during the drying process;
Flammable liquids storage (except as provided in Section 15-24-270 of this Code);
Fume or flammable compressed gas;
Grinding or dust producing;
Hazardous chemical;
Highly flammable material storage;
Highly toxic materials;
Japanning or enameling;
Nitrocellulose products;
Paint spraying or mixing except for water base paint;
Picker or shredder;
Standard fireproof vault;
Sulphur storage;
shall be located in any story below grade in any building hereafter designed, erected, altered or converted for any purpose; provided, however, that one or more rooms built for no purpose other than that of the operation of water purification plants or a refrigerating unit may be located in any basement of any building.