Loading...
Every room in a dry cleaning building in which a flammable solvent having a flash point below 140 degrees Fahrenheit (closed cup tester) is used shall be provided with an exit directly to the outside of the building. Every door to such a room shall open outward. Any stairway for such a building shall be a smokeproof tower or exterior stairway. There shall be no window or ventilating opening within five feet of any such stairway. An open balcony or runway leading to a stairway shall be considered as such means of exit, but there shall be no window or ventilating opening upon or below such balcony.
(Prior code § 60-29)
Every room used for the examining or repairing of motion picture films shall have not less than two exit doorways, located as required by Section 13-112-270 and one of such exits shall lead directly to a vertical means of exit or to the outside of the building. Any such room shall not have any exit into or through another nitrocellulose products room, excepting a receiving, shipping or distributing room having such products in closed containers.
(Prior code § 60-30)
ARTICLE V. ARTIFICIAL LIGHTING AND EXIT SIGNS (13-112-320 et seq.)
Every vertical means of exit required under that part of this chapter dealing with means of exit from any story for which two exits are required shall have a standard exit sign as required by Chapter 13-160.
(Prior code § 60-34)
Loading...