Skip to code content (skip section selection)
Compare to:
Chicago Overview
Prior Chicago Building Code
BUILDING CODE AND RELATED EXCERPTS OF THE MUNICIPAL CODE OF CHICAGO
DIVISION 1 - ADMINISTRATION
DIVISION 2 - DEFINITIONS
DIVISION 3 - USE AND OCCUPANCY CLASSIFICATIONS
DIVISION 4 - SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY
DIVISION 5 - GENERAL BUILDING HEIGHTS AND AREAS
DIVISION 6 - TYPES OF CONSTRUCTION
DIVISION 7 - FIRE-RESISTANCE-RATED CONSTRUCTION
DIVISION 8 - INTERIOR FINISHES (NA)
DIVISION 9 - FIRE PROTECTION SYSTEMS
DIVISION 10 - MEANS OF EGRESS
DIVISION 11 - ACCESSIBILITY
DIVISION 12 - INTERIOR ENVIRONMENT
DIVISION 13 - ENERGY EFFICIENCY AND ENVIRONMENTAL PROTECTION
DIVISION 14 - EXTERIOR WALLS (NA)
DIVISION 15 - ROOF ASSEMBLIES AND ROOFTOP STRUCTURES (NA)
DIVISION 16 - STRUCTURAL DESIGN
DIVISION 17 - STRUCTURAL TESTS AND SPECIAL INSPECTIONS
DIVISION 18 - SOILS AND FOUNDATIONS
DIVISION 19 - CONCRETE
DIVISION 20 - ALUMINUM (NA)
DIVISION 21 - MASONRY
DIVISION 22 - STEEL
DIVISION 23 - WOOD
DIVISION 24 - GLASS AND GLAZING (NA)
DIVISION 25 - GYPSUM BOARD AND PLASTER (NA)
DIVISION 26 - PLASTIC (NA)
DIVISION 27 - ELECTRICAL
DIVISION 28 - MECHANICAL SYSTEMS
CHAPTER 18-28 MECHANICAL SYSTEMS*
Article I. Administration (18-28-101 et seq.)
Article II. Definitions (18-28-201 et seq.)
Article III. General Regulations (18-28-301 et seq.)
Article IV. Ventilation (18-28-401 et seq.)
Article V. Exhaust Systems (18-28-501 et seq.)
Article VI. Duct Systems (18-28-601 et seq.)
Article VII. Combustion Air (18-28-701 et seq.)
Article VIII. Chimneys and Vents (18-28-801 et seq.)
Article IX. Specific Appliances, Fireplaces and Solid Fuel-Burning Equipment (18-28-901 et seq.)
Article X. Boilers, Water Heaters and Pressure Vessels (18-28-1001 et seq.)
Article XI. Refrigeration (18-28-1101 et seq.)
18-28-1101 General.
18-28-1101.1 Scope.
18-28-1101.2 Standards for Pressure Vessels.
18-28-1101.3 Protection.
18-28-1101.4 Fuel gas connection.
18-28-1101.5 Signage - General.
18-28-1101.6 Condensate disposal.
18-28-1101.7 General.
18-28-1101.8 Ammonia dump valve.
18-28-1101.9 Maintenance.
18-28-1101.10 Location of condensing unit.
18-28-1101.11 Stairways and exitways.
18-28-1101.12 General limitations.
18-28-1101.13 Refrigerant discharge.
18-28-1101.14 Safety equipment.
18-28-1101.15 Recirculation of water used for cooling purposes.
18-28-1102 System Requirements.
18-28-1102.1 General.
18-28-1102.2 Refrigerants.
18-28-1102.2.1 Mixing.
18-28-1102.3 Pressure relief.
18-28-1102.3.1 Discharge piping.
18-28-1102.3.2 Sizing.
18-28-1103 Refrigeration System Classification.
18-28-1103.1 Refrigerant classification.
18-28-1103.2 Occupancy classification.
18-28-1103.2.1 Institutional systems - general.
18-28-1103.2.2 Industrial systems - general.
18-28-1103.2.3 Commercial systems - general.
18-28-1103.2.4 Multiple dwelling systems - general.
18-28-1103.3 System classification.
18-28-1103.3.1 Low-probability systems.
18-28-1103.3.2 High-probability systems.
18-28-1104 System Application Requirements.
18-28-1104.1 General.
18-28-1104.2 Machine room.
18-28-1104.2.1 Institutional occupancies.
18-28-1104.2.2 Industrial occupancies and refrigerated rooms.
18-28-1104.2.3 Multiple dwelling location provisions.
18-28-1104.3 Refrigerant restrictions.
18-28-1104.3.1 Air-conditioning for human comfort.
18-28-1104.3.2 Nonindustrial occupancies.
18-28-1104.3.3 All occupancies.
18-28-1104.3.4 Protection from refrigerant decomposition.
18-28-1104.4.
18-28-1104.4.1 Nonconnecting spaces.
18-28-1104.4.2 Ventilated spaces.
18-28-1104.4.3 Closures.
18-28-1104.4.4 Plenums.
18-28-1104.4.5 Supply and return ducts.
18-28-1105 Machinery Room General Requirements.
18-28-1105.1 Access.
18-28-1105.2 Dimensions.
18-28-1105.3 Doors.
18-28-1105.4 Openings.
18-28-1105.5 Refrigerant detector.
18-28-1105.6 Tests.
18-28-1105.7 Fuel-burning appliance.
18-28-1105.8 Ventilation.
18-28-1105.8.1 Discharge location.
18-28-1105.8.2 Make-up air.
18-28-1105.8.3 Quantity - Normal ventilation.
18-28-1105.8.4 Quantity - Emergency conditions.
18-28-1105.9 Termination of relief devices.
18-28-1105.10 Ammonia discharge.
18-28-1105.11 Safety equipment.
18-28-1106 Machinery Room Special Requirements.
18-28-1106.1 General.
18-28-1106.2 Elevated temperature.
18-28-1106.3 Construction requirements.
18-28-1106.4 Opening protectives.
18-28-1106.5 Pipe penetrations.
18-28-1106.6 Deliberately omitted.
18-28-1106.7 Egress.
18-28-1106.8 Ammonia room ventilation.
18-28-1106.9 Flammable refrigerants.
18-28-1106.10 Remote controls.
18-28-1106.10.1 Refrigeration system.
18-28-1106.10.2 Ventilation system.
18-28-1106.11 Fireman's dump system.
18-28-1106.12 Hand-operated emergency valves.
18-28-1106.12.1 Hand-operated emergency valve discharge - Group 1 refrigerants.
18-28-1106.13 Provisions for discharge of refrigerants.
18-28-1107 Refrigerant Piping.
18-28-1107.1 General.
18-28-1107.2 Pipe enclosures.
18-28-1107.2.1 Location prohibition.
18-28-1107.3 Condensation.
18-28-1107.3.1 Cooling coil condensation requirements.
18-28-1107.4 Materials for refrigerants pipe and tubing.
18-28-1107.4.1 Steel pipe.
18-28-1107.4.2 Copper and brass pipe.
18-28-1107.4.3 Copper tube.
18-28-1107.4.4 Copper tube joints.
18-28-1107.4.5 Aluminum tube.
18-28-1107.5 Joints and refrigerant-containing parts in air ducts.
18-28-1107.6 Exposure of refrigerant pipe joints.
18-28-1107.7 Stop valves.
18-28-1107.7.1 Liquid receivers.
18-28-1107.7.2 Copper tubing.
18-28-1107.7.3 Identification.
18-28-1108 Field Test.
18-28-1108.1 General.
Article XII. Hydronic Piping (18-28-1200 et seq.)
Article XIII. Fuel Oil Piping and Storage (18-28-1301 et seq.)
Article XIV. Fuel-Gas Piping (18-28-1401 et seq.)
Article XV. Solar Systems (18-28-1501 et seq.)
DIVISION 29 - PLUMBING SYSTEMS
DIVISION 30 - ELEVATORS AND CONVEYING SYSTEMS
DIVISION 31 - SPECIAL CONSTRUCTION (NA)
DIVISION 32 - ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
DIVISION 33 - SAFEGUARDS DURING CONSTRUCTION
DIVISION 34 - EXISTING STRUCTURES
DIVISION 35 - REFERENCED STANDARDS

You are viewing an archived code

Loading...
18-28-1105.8.2  Make-up air.
   Provisions shall be made for make-up air to replace the air that is being exhausted. Openings for make-up air shall be located to avoid intake of exhaust air. Supply and exhaust ducts to the machinery room shall serve no other area, shall be constructed in accordance with Article 5 and shall be covered with corrosion-resistant screen of not less than 1/4-inch (6.4 mm) mesh.
18-28-1105.8.3  Quantity – Normal ventilation.
   During occupied conditions, the mechanical ventilation system shall exhaust the larger of the following:
   1.   Not less than 0.5 cfm per square foot (0.0025 m 3 /s m 2 ) of machinery room area or 20cfm (0.009 m 3 /s) per person; or
   2.   A volume required to limit the room temperature rise to 18°F (10°C) taking into account the ambient heating effect of all machinery in the room.
18-28-1105.8.4  Quantity – Emergency conditions.
   Upon actuation of the refrigerant detector required in Section 18-28-1105.5, the mechanical ventilation system shall exhaust air from the machinery room in the following quantity:
where:
   Q = The airflow in cubic feet per minute (m3/s).
   G = The design mass of refrigerant in pounds (kg) in the largest system, any part of which is located in the machinery room.
18-28-1105.9  Termination of relief devices.
   Pressure-relief devices, and purge systems located within the machinery room shall terminate outside of the structure at a location not less than 15 feet (4572 mm) above the adjoining grade level and not less than 20 feet (6096 mm) from any window, ventilation opening or exit.
18-28-1105.10  Ammonia discharge.
   Pressure-relief valves for ammonia systems shall discharge in accordance with ASHRAE 15. Piping from Ammonia Refrigerant (Group B2) shall terminate above the roof of the highest story of the building and shall be at least 40 feet (12.192m) from any adjoining building which extends above the roof and at least 40 feet (12.192m) from any penthouse, skylight, fixed ladder or exhaust duct system. Piping shall terminate downward at an angle of 45 degrees from the horizontal, and shall be provided with a permanent warning sign attached to the piping at the point of termination. The sign shall have a yellow background and shall state in black letters not less than 3 inches (76.2 mm) in height in both Spanish and English.
 
AMMONIA VENT - DANGER

AMONIACO DESCARGA - PELIGRO
 