18-28-1106.12  Hand-operated emergency valves.
   All Direct Expansion Refrigeration Systems containing more than 100 pounds (45.36 kg) of refrigerant shall be provided with a hand operated emergency valve. Such device shall be connected to the low side of the refrigeration system and be located where the emergency valve is readily available for Fire Department use. Valves shall be identified and operating instructions for the use of the emergency valve shall be provided at the location of the valve. Hand operated emergency valves shall be of the following sizes and a maximum inlet pipe length of one hundred (100) feet (30.48m):
 
Pounds of Refrigerant In System
Valve Size
100 – 200
1 inch nominal pipe size
201 – 300
1 1/4 inches nominal pipe size
301 – 500
1 1/2 inches nominal pipe size
501 – 1,000
2 inches nominal pipe size
above 1,000
3 inches nominal pipe size