18-28-1101.10  Location of condensing unit.
   The condensing unit of every refrigeration system shall be placed in a readily accessible location and such location shall be provided with adequate means of ventilation and light Refrigerating equipment containing over 10 pounds (4.536 kg) of refrigerant shall not be located in retail areas or other areas routinely accessed by the general public. No refrigeration system shall be placed under or on stairways, stairway lands, under or on fire escape passageways, entrance or exits of buildings, unless it is a self-contained system servicing that stairway.