18-28-1103.1  Refrigerant classification.
   Refrigerants shall be classified in accordance with ASHRAE 34 as listed in Table 18-28-1103.1.
Table 18-28-1103.1
Refrigerant and Amounts
Refrigerant Number
Chemical Name
Chemical Formula
Quantity of Refrigerant per Occupied Space
Pounds per 1,000 Cubic Feet
Ppm by Volume
g/m3 A, C
Refrigerant Number
Chemical Name
Chemical Formula
Quantity of Refrigerant per Occupied Space
Pounds per 1,000 Cubic Feet
Ppm by Volume
g/m3 A, C
Group A1
R-11
Trichlorofluoromethane
CCl3F
1.6
4,000
25
R-12
Dichlorodifluoromethane
CCl2F2
12
40,000
200
R-13
Chlorotrifluoromethane
CClF3
18
67,000
290
R-13B1
Bromotrifluoromethane
CBrF3
22
57,000
350
R-14
Tetrafluoromethane (carbon tetrafluoride)
CF4
15
67,000
240
R-22
Chlorodifluoromethane
CHClF2
9.4
42,000
150
R-113
Trichlorotrifluoromethane
CCl2FCCIF2
1.9
4,000
31
R-114
Dichlorotetrafluoroethane
CClF2CCIF2
9.4
21,000
150
R-123
2,2-dichloro-1,1,1-trifluoroethane
CHCl2CF3
0.4
1,000
6.3
R-134a
1,1,1,2-tetrafluoroethane
CH2FCF3
16
60,000
250
R-400
R-12 and R-114
CCI2F2/C2CI2F4
d
d
d
R-500
R-12/152a (73.8/26.2)
CCI2F2/CH3CHF2
12
47,000
200
R-502
R-22/115 (48.8/51.2)
CHCIF2/CCIF2CF3
19
65,000
300
R-503
R-23/13(40.1/59.9)
CHF3/CCIF3
15
67,000
240
R-718
Water
H2O
f
f
f
R-744
Carbon Dioxide
CO2
5.7
50,000
91
Group A2
R-142b
1-Chloro-1,1,-Difluoroethane
CH3CCIF2
3.7
14,000
60
R-152a
1,1-Difluoroethane
CH3CHF2
1.2
7,000
20
Group A3
R-170
Ethane
C2H6
0.50
6,400
8.0
R-290
Propane
C3H8
0.50
4,400
8.0
R-600
Butane
C4H10
0.51
3,400
8.2
R-600a
2-Methyl propane (Isobutane)
CH(CH3)3
0.51
3,400
8.2
R-1150
Ethene (Ethylene)
C2H4
0.38
5,200
6.0
R-1270
Propene (Propylene)
C3H6
0.37
3,400
5.9
Group B1
R-123
2,2-Dichloro-1,1,1-Trifluoroethane
CHCI2CF3
0.40
1,000
6.3
R-764
Sulfur Dioxide
SO2
0.016
100
0.26
Group B2
R-40
Chloromethane (Methyl Chloride)
CH3CI
1.3
10,000
21
R-611
Methyl Formate
HCOOCH3
0.78
5,000
12
R-717
Ammonia
NH3
0.022
500
0.35
 
a The refrigerant safety groups in Table 1 are not part of ASHRAE Standard 15. The classifications shown are from ASHRAE Standard 34, which governs in the event of a difference.
b To be used only in conjunction with Section 7.
c To correct for height, H(ft), above sea level, multiply these values by (1 - 2.42 x 1 0-6 H). To correct for height, H(km), above sea level, multiply these values by (1 - 7.94 x 1 0-2 h).
d The quantity of each component shall comply with the limits set in Table 1 for the pure compound, and the total volume % of all components shall be calculated per Appendix A (not to exceed 67,000 ppm by volume for any refrigerant blend).
e The basis of the table quantities is a single event where a complete discharge of any refrigerant system into the occupied space occurs. The quantity of refrigerant is the most restrictive of a minimum oxygen concentration of 19.5% or as follows:
   Group 1      –   80% of the cardiac sensitization level for R-11, R-12, R-13B1, R-22, R-113, R-114, R-134a, R-500, and R-502. 100% of the IDLH(21) for R-744. Others are limited by levels where oxygen deprivation begins to occur.
   Group A2, A3      –   Approximately 20% of LFL.
   Group B1      –   100% of IDLH for R-764, and 100% the measure consistent with the IDLH for R-123.
   Groups B2, B3   –   100% of IDLH or 20% of LFL, whichever is lower.
f The quantity is unlimited when R-718 (water) is used as the refrigerant.