Skip to code content (skip section selection)
Compare to:

You are viewing an archived code

18-28-1104.4.2  Ventilated spaces.
   Where a refrigerating system or a part thereof is located within an air handler, an air distribution duct system, or in an occupied space served by a mechanical ventilation system, the entire air distribution system shall be analyzed to determine the worst case distribution of leaked refrigerant. The worst case or the smallest volume in which the leaked refrigerant disperses shall be used to determine the refrigerant quantity limit in the system, subject to the following criteria.