ARTICLE XIX. PARKING FACILITIES (13-96-880 et seq.)
Every parking facility hereafter erected shall comply with all applicable provisions of this Code and with the special provisions of Sections 13-96-890 to 13-96-1030, inclusive.
(Prior code § 61-20)
“Catwalk” means a footway above ground floor.
“Dry standpipe” means a pipe extending full height of a building to which fire hose can be attached and which, when not in operation, is free from water to prevent freezing.
“Hoist type” means a parking structure in which mechanical lift equipment provides a combination vertical and horizontal operation for semi-automatic parking of vehicles in a multi-level structure.
“Manlift” means a continuous belt-driven lifting device used for transmitting attendants between various levels.
“Parking facility” means a multi-level structure in which each level is used primarily for the purpose of storing passenger motor vehicles, and which does not necessarily have enclosing walls.
“Parking level” means a floor in a structure on which vehicles are parked.
“Ramp type” means a parking structure provided with inclined driveway for transporting vehicles to various parking levels.
(Prior code § 61-20.1)
Structures shall be of Type I-A fire-resistive construction, as defined in Chapter 13-60.
(Prior code § 61-20.2)
A standard automatic sprinkler system shall not be required in these facilities except where the vehicle storage area on more than four levels is enclosed on all sides. A standard inside standpipe system, as required by the provisions of this Code shall not be required in these unheated automobile parking facilities; provided, however, that a dry standpipe system, as approved by the fire commissioner, shall be required in such facilities which are in excess of 80 feet in height.