13-96-930  Ventilation.
   Ventilation, as defined in Chapter 18-28 shall be required only when the openings in the exterior walls on a level are less than 20 percent of the total external wall area on such level. The location of such openings shall be well distributed.
(Prior code § 61-20.5; Amend Coun. J. 11-9-16, p. 36266, § 20)
13-96-940  Emergency lighting.
   Emergency lighting shall comply with System III as defined in Section 14E-7-700.
(Prior code § 61-20.6; Amend Coun. J. 6-14-95, p. 2841; Amend Coun. J. 11-9-16, p. 36266, § 20; Amend Coun. J. 9-6-17, p. 55278, Art. II, § 35)
13-96-950  Guards and gates.
   Access from one side of the hoistway to the other side, in each level, shall be provided by a catwalk at each end of the structure. Hoistways shall be protected with incombustible gates and guards.
(Prior code § 61-20.7)
13-96-960  Stairways.
   Two stairways, not less than 30 inches wide from lowest to uppermost level shall be required for each parking structure. These stairways may be of open riser and open grille tread type. There shall be a one-hour fire-resistive wall enclosure separating stairways from parking levels.
(Prior code § 61-20.8)