710.2 Future fixtures.
Where provision is made for the future installation of fixtures, those provided for shall be considered in determining the required sizes of drain pipes.
711.1 Horizontal branch connections above or below vertical stack offsets.
If a horizontal branch connects to the stack within 2 feet (610 mm) above or below a vertical stack offset, and the offset is located more than four branch intervals below the top of the stack, the offset shall be vented in accordance with Section 907.
711.1.1 Omission of vents for vertical stack offsets.
Vents for vertical offsets required by Section 711.1 shall not be required where the stack and its offset are sized as a building drain (see Table 710.1(1), Column 5).