5904.1 Indoor storage.
Indoor storage of flammable solids in amounts exceeding the maximum allowable quantity per control area indicated in FC Table 5003.1.1(1) shall be in accordance with FC 5001, 5003, 5004, this chapter, and NFPA 484.
5904.1.1 Pile size limits and location.
Flammable solids stored in quantities greater than 1,000 cubic feet (28 m
3) shall be separated into piles each not larger than 1,000 cubic feet (28 m3).
5904.1.2 Aisles.
Aisle widths between piles shall not be less than the height of the piles or 10 feet (3048 mm), whichever is greater.
5904.1.3 Basement storage.
Flammable solids shall not be stored in basements or other areas below grade.
5904.2 Outdoor storage.
Outdoor storage of flammable solids in amounts exceeding the maximum allowable quantities per control area indicated in FC Table 5003.1.1(3) shall be in accordance with FC 5001, 5003, 5004, this chapter, and NFPA 484.