2107.2.2 Means of egress.
Type II dry cleaning rooms shall have not less than two means of egress through doors located at opposite ends of the room, at least one of which shall lead directly to the outdoors.
2107.2.3 Spill control and secondary containment.
Curbs, drains, or other provisions for spill control and secondary containment shall be provided in accordance with FC 5004.2 to collect solvent leakage and fire protection water and direct it to a safe location.
2107.3 Solvent storage tanks.
Solvent storage tanks for Class II, IIIA and IIIB liquids shall conform to the requirements of FC Chapter 57 and be located underground, or outdoors, aboveground.
Exception: Indoor storage tanks in compliance with the requirements of NFPA 32 and FC Chapter 57.
2108.1 General.
Where required by this section, fire protection devices, equipment and systems shall be designed, installed, operated and maintained in accordance with FC Chapter 9 and the construction codes, including the Building Code.
2108.2 Fire extinguishing systems in newly-established dry cleaning facilities.
Dry cleaning facilities established after the effective date of FC 2108.2 shall be protected throughout by a sprinkler system, provided, however, that a heretofore lawfully-existing dry cleaning establishment in a newly-established facility may comply with the requirements of FC 2108.3 if the newly-established facility does not constitute a change in the use or occupancy of the premises, as determined by the Department of Buildings. The sprinkler system shall be designed and installed in accordance with the Building Code.