Skip to code content (skip section selection)
Compare to:
Los Angeles Overview
Los Angeles Charter and Administrative Code
Los Angeles Municipal Code
MUNICIPAL CODE
FOREWORD
CHAPTER I GENERAL PROVISIONS AND ZONING
CHAPTER 1A CITY OF LOS ANGELES ZONING CODE
CHAPTER II* LICENSES, PERMITS, BUSINESS REGULATIONS
CHAPTER III PUBLIC HEALTH CODE
CHAPTER IV PUBLIC WELFARE
CHAPTER V PUBLIC SAFETY AND PROTECTION
CHAPTER VI PUBLIC WORKS AND PROPERTY
CHAPTER VII TRANSPORTATION
CHAPTER VIII TRAFFIC
CHAPTER IX BUILDING REGULATIONS
ARTICLE 1 BUILDINGS [BUILDING CODE]
ARTICLE 1.2 EXISTING BUILDING CODE
ARTICLE 1.5 LOS ANGELES RESIDENTIAL CODE
ARTICLE 2 ELEVATOR CODE
ARTICLE 3 ELECTRICAL CODE
ARTICLE 4 PLUMBING CODE
ARTICLE 5 MECHANICAL CODE
ARTICLE 6 MISCELLANEOUS
ARTICLE 7 BOILERS, UNFIRED PRESSURE VESSELS AND OTHER EQUIPMENT
ARTICLE 8 GENERAL ADMINISTRATIVE PROVISIONS
ARTICLE 9 GREEN BUILDING CODE
CHAPTER X BUSINESS REGULATIONS
CHAPTER XI NOISE REGULATION
CHAPTER XII THE WATER CONSERVATION PLAN OF THE CITY OF LOS ANGELES
CHAPTER XIII THE EMERGENCY ENERGY CURTAILMENT PLAN OF THE CITY OF LOS ANGELES
CHAPTER XV RENT STABILIZATION ORDINANCE
CHAPTER XVI HOUSING REGULATIONS
CHAPTER XVII RULES AND REGULATIONS GOVERNING THE USE OF THE LOS ANGELES AIRPORTS
CHAPTER XVIII EMPLOYEE WAGES AND PROTECTIONS
CHAPTER XIX ENVIRONMENTAL PROTECTION
CHAPTER XX COVID-19 PROTECTION AND RECOVERY*
TABLES
Los Angeles Planning and Zoning
Chapter 1A City of Los Angeles Zoning Code
Table of Amending Legislation for Chapter 1A
Loading...
SEC. 94.2000.0. GENERAL.
 
 
SEC. 94.2001.0. SCOPE.
   (Added by Ord. No. 185,198, Eff. 11/22/17.)
 
   The standards of this Division 20 provide the minimum requirements for the design and installation of automatic fire protection systems. The design of all fire protection systems shall be in conformity with accepted engineering practices and the provisions of the LAMC.
 
   Automatic fire sprinkler systems shall be installed in locations required by the Los Angeles Building Code, and all fire sprinkler systems shall be in conformance with the approved plans and the LAMC.
 
 
SEC. 94.2005.0. LOCATION.
 
   No fire protection system shall be located on any lot other than the lot that is the site of the building, structure or premises served by that system.
 
 
SEC. 94.2006.0. [PROTECTION FROM MECHANICAL DAMAGE.]
 
   All fire-protection equipment and piping shall be adequately protected from mechanical damage.
 
 
SEC. 94.2010.0. NFPA 13.
   (Amended by Ord. No. 187,719, Eff. 1/23/23.)
 
   Chapter 35 of the 2022 California Building Code to the extent it adopts and amends NFPA 13 is adopted by reference and the following Subsections are added to read as follows:
 
94.2010.1. Comply with the sprinkler provisions in Chapters 4 and 9 of the 2022 California Building Code as they pertain to sprinkler systems.
 
94.2010.2. NFPA 13 Section 3.3.243 is added to read as follows:
 
   3.3.243. Water Curtain is a line of closely spaced fire sprinklers (or a single sprinkler) aligned adjacent to openings to keep fire from penetrating those openings.
 
94.2010.3. NFPA 13 Section 9.3.5.5 is added to read as follows:
 
   9.3.5.5. Water curtains shall consist of closely spaced sprinklers and draft stops that are made of noncombustible or limited combustible material. The draft stops shall be located immediately adjacent to the opening and shall be at least 18 inches (47.2 mm) deep measured from the sprinkler deflector to the bottom of the draft stop and shall be of noncombustible or limited-combustible material. Sprinklers shall be spaced not more than 6 feet (1929.8 mm) apart and placed 6 to 12 inches (152.4 mm to 304.8 mm) from the draft stop on the side away from the opening. Where sprinklers are closer than 6 feet (1828.8 mm), cross baffles shall be provided in accordance with NFPA 13 Section 10.2.5.4.2.
 
94.2010.4. NFPA 13 Section 16.9.10.5 is added to read as follows:
 
   Locations. Floor control valves shall be within a stairway enclosure or within the vestibule or on the access balcony of a smoke proof enclosure.
 
   EXCEPTIONS:
 
   1.   In buildings with three or fewer stories or where there is no stairway that serves a floor, control valves may be located elsewhere on the floor level.
 
   2.   Unenclosed stairways in parking garages.
 
94.2010.5. NFPA 13 Section 19.3.3.6 is added to read as follows:
 
   19.3.3.6. Water curtains shall be hydraulically calculated in accordance with NFPA 13 Section 19.3.
 
 
SEC. 94.2013.0. NFPA 13R.
   (Amended by Ord. No. 187,719, Eff. 1/23/23.)
 
   Chapter 35 of the 2022 California Building Code to the extent it adopts and amends NFPA 13R is adopted by reference and LAMC Subsection 94.2013.1 is added to read as follows:
 
94.2013.1. Comply with the sprinkler provisions in Chapters 4 and 9 of the 2022 California Building Code as they pertain to NFPA 13R.
 
 
SEC. 94.2014.0. NFPA 13D.
   (Amended by Ord. No. 187,719, Eff. 1/23/23.)
 
   Chapter 35 of the 2022 California Building Code to the extent it adopts and amends NFPA 13D is adopted by reference and LAMC Subsection 94.2014.1 is added to read as follows:
 
94.2014.1. Comply with the sprinkler provisions in Chapters 4 and 9 of the 2022 California Building Code as they pertain to sprinkler systems in residential occupancies within the scope of NFPA 13D.
 
 
SEC. 94.2020.0. NFPA 14.
   (Amended by Ord. No. 187,719, Eff. 1/23/23.)
 
   Chapter 35 of the 2022 California Building Code to the extent it adopts and amends NFPA 20 is adopted by reference and the following Los Angeles Municipal Code subsections are added to read as follows:
 
94.2020.1. Comply with the fire sprinkler provisions in Chapters 4, 9, and 33 of the 2022 California Building Code as they pertain to NFPA 14.
 
94.2020.2. NFPA 14 Section 6.4.5.3.1 is hereby added to read as follows:
 
   6.4.5.3.1. Where the Fire Department inlet connection does not serve the entire building, the portion served shall be suitably identified.
 
94.2020.3. NFPA 14 Section 9.1.5 is hereby added to read as follows:
 
   9.1.5. Water supplies from the following sources shall be permitted:
 
   1.    A public waterworks system where pressure and flow rate are adequate;
 
   2.    Automatic fire pumps connected to an approved water source in accordance with NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection.
 
94.2020.4. Pressure Regulator Hose Valve Test.
 
94.2020.4.1. Test Required. When required by the Fire Department, 2 1/2 inch (63.5 mm) pressure regulator hose valves installed on standpipe outlets shall be tested for proper operation at a flow of 300 g.p.m. with a minimum residual pressure of 125 psi in the presence of a representative of the Fire Department.
 
94.2020.4.2. Safety. Test nozzles and other equipment shall be adequately secured so as to eliminate danger to personnel.
 
94.2020.4.3. Opening. An accessible 2 1/2 inch (63.5 mm) capped or plugged test opening shall be installed adjacent to each pressure regulator valve.
 
94.2020.4.4. Drain. The test openings shall drain to a minimum 3 inch (76.2 mm) drain line constructed and installed as required for fire sprinkler drains. The drains shall not discharge where they may cause damage. Where available, drains shall terminate to the fire water storage tank. When test openings are located below tank elevation alternate means for testing and drainage shall be provided as needed.
 
94.2020.4.5. Interconnection. TThe test drain shall either be separate or connect to a fire sprinkler drain. Low point Auxiliary drains shall be added if required.
 
94.2020.5. NFPA 14 Section 11.2.3 is amended to read as follows:
 
   11.2.3. Flushing the System Riser. Water shall flow from the topmost outlet of each riser until the system is clear of debris.
 
   11.2.3.1. Roof Outlets. Standpipe risers going through the last floor of the building, through a floor under a roof, or adjacent to a roof shall be designed so that they can be flushed through outlets located on roof.
 
   11.2.3.2. Flow. All standpipes shall be flushed individually through the roof, or in the absence of roof outlets, through the topmost outlet at a residual pressure of at least 65 psi. The flow for Class I and Class III standpipes shall be at least 500 g.p.m through each riser.
 
 
SEC. 94.2030.0. FIRE PUMPS AND DRIVERS.
   (Amended by Ord. No. 187,719, Eff. 1/23/23.)
 
   Chapter 35 of the 2022 California Building Code to the extent it adopts and amends NFPA 20 is adopted by reference and Los Angeles Municipal Code Subsections 94.2030.1, 94.2030.2, and 94.2030.3 are amended or added to read as follows:
 
94.2030.1. Comply with the fire pump provisions in Chapters 4 and 9 of the 2022 California Building Code.
 
94.2030.2. NFPA 20 Sec. 3.16.11 is added to read as follows:
 
   3.16.11. Fire Department Connections. Fire Department connections shall not be connected to on suction side of the pump.
 
94.2030.3. The discharge from the test header shall terminate to the fire storage tank when available and shall be readily accessible for testing and maintenance.
 
 
Loading...