(Added by Ord. No. 185,198, Eff. 11/22/17.)
The standards of this Division 20 provide the minimum requirements for the design and installation of automatic fire protection systems. The design of all fire protection systems shall be in conformity with accepted engineering practices and the provisions of the LAMC.
Automatic fire sprinkler systems shall be installed in locations required by the Los Angeles Building Code, and all fire sprinkler systems shall be in conformance with the approved plans and the LAMC.
(Amended by Ord. No. 187,719, Eff. 1/23/23.)
Chapter 35 of the 2022 California Building Code to the extent it adopts and amends NFPA 13 is adopted by reference and the following Subsections are added to read as follows:
3.3.243. Water Curtain is a line of closely spaced fire sprinklers (or a single sprinkler) aligned adjacent to openings to keep fire from penetrating those openings.
9.3.5.5. Water curtains shall consist of closely spaced sprinklers and draft stops that are made of noncombustible or limited combustible material. The draft stops shall be located immediately adjacent to the opening and shall be at least 18 inches (47.2 mm) deep measured from the sprinkler deflector to the bottom of the draft stop and shall be of noncombustible or limited-combustible material. Sprinklers shall be spaced not more than 6 feet (1929.8 mm) apart and placed 6 to 12 inches (152.4 mm to 304.8 mm) from the draft stop on the side away from the opening. Where sprinklers are closer than 6 feet (1828.8 mm), cross baffles shall be provided in accordance with NFPA 13 Section 10.2.5.4.2.
Locations. Floor control valves shall be within a stairway enclosure or within the vestibule or on the access balcony of a smoke proof enclosure.
EXCEPTIONS:
1. In buildings with three or fewer stories or where there is no stairway that serves a floor, control valves may be located elsewhere on the floor level.
2. Unenclosed stairways in parking garages.
19.3.3.6. Water curtains shall be hydraulically calculated in accordance with NFPA 13 Section 19.3.
(Amended by Ord. No. 187,719, Eff. 1/23/23.)
Chapter 35 of the 2022 California Building Code to the extent it adopts and amends NFPA 13R is adopted by reference and LAMC Subsection 94.2013.1 is added to read as follows:
(Amended by Ord. No. 187,719, Eff. 1/23/23.)
Chapter 35 of the 2022 California Building Code to the extent it adopts and amends NFPA 13D is adopted by reference and LAMC Subsection 94.2014.1 is added to read as follows: