Bather preparation facilities serving nonprivate swimming pools with a bather load greater than 200 shall be designed so that passage from the showers to the swimming facility shall not be through dressing room areas and other dry areas of the bather preparation facility.
(Added Coun. J. 10-14-21, p. 37722, Art. XII, §1)
Bather preparation facilities shall be provided with at least the number of showers, water closets, urinals and lavatories indicated in Table 18-29-1203.3. Showers and lavatories shall be provided with liquid or powdered soap dispensers. Showers shall be supplied with tempered water or hot water.
Bather Load a | Fixtures Required (Male) b | Fixtures Required (Female) b | |||||
Water Closets | Urinals | Lavatories | Showers | Water Closets | Lavatories | Showers |
Bather Load a | Fixtures Required (Male) b | Fixtures Required (Female) b | |||||
Water Closets | Urinals | Lavatories | Showers | Water Closets | Lavatories | Showers | |
0 - 100 | 1 | 0 | 1 | 1 | 1 | 1 | 1 |
101 - 200 | 1 | 1 | 1 | 2 | 2 | 1 | 2 |
201 - 300 | 1 | 2 | 2 | 3 | 3 | 2 | 3 |
301 - 400 | 2 | 2 | 2 | 4 | 4 | 2 | 4 |
401 - 500 | 2 | 3 | 2 | 5 | 5 | 2 | 5 |
501 - 1,000 | 3 | 3 | 2 | 6 | 6 | 2 | 6 |
1001 - 1,500 | 4 | 5 | 2 | 10 | 9 | 2 | 10 |
1,501 - 2,000 | 5 | 6 | 2 | 15 | 11 | 2 | 15 |
2,001 or more | 6 | 7 | 3 | 20 | 13 | 3 | 20 |
a. Bather load shall be determined in accordance with Section 1004 of the Chicago Building Code.
b. Single-user toilet rooms and single-user bathing rooms may be provided in accordance with Section 18-29-403.1.3. In such case, water closets shall be provided instead of required urinals.
(Added Coun. J. 10-14-21, p. 37722, Art. XII, §1)
At a facility used by school classes, one shower for every four persons in the largest class shall be provided for each sex, except that in no case shall the number of showers provided be less than shown in Table 18-29-1203.3.
(Added Coun. J. 10-14-21, p. 37722, Art. XII, §1)
A foot spray, if provided, shall be supplied from the potable water system or the swimming facility recirculation system, have a spray head 18 to 24 inches (457 to 610 mm) above the walking surface, have a conveniently located valve, be arranged to spray the bathers from knees to feet as they enter the enclosure, and have a drain.
(Added Coun. J. 10-14-21, p. 37722, Art. XII, §1)