Stair treads and risers must be of uniform size and shape. The variance between the largest and smallest riser height or between the largest and smallest tread depth must not exceed 1/2 inch (13 mm) in any flight of stairs.
Exception: Conditions allowed by the Chicago Building Code.
Existing stairways may be rebuilt. The replacement of an existing stairway is not required to comply with the new stairway requirements of the Chicago Building Code where the existing space and construction will not allow a reduction in pitch or slope or elimination of winders.
Usable space under interior stairways must be separated from the stairway with 1-hour fire-resistance-rated construction. Access to enclosed spaces beneath enclosed interior stairways may not be provided from within the stairway enclosure.
Enclosed usable space under exterior stairways must be completely enclosed in 1-hour fire-resistance-rated construction. Open space under exterior stairways may not be used for any purpose.