Skip to code content (skip section selection)
Compare to:
Chicago Overview
Municipal Code of Chicago
MUNICIPAL CODE OF CHICAGO
TITLE 1 GENERAL PROVISIONS
TITLE 2 CITY GOVERNMENT AND ADMINISTRATION
TITLE 3 REVENUE AND FINANCE
TITLE 4 BUSINESSES, OCCUPATIONS AND CONSUMER PROTECTION
TITLE 5 HOUSING AND ECONOMIC DEVELOPMENT
TITLE 6 HUMAN RIGHTS*
TITLE 7 HEALTH AND SAFETY
TITLE 8 OFFENSES AFFECTING PUBLIC PEACE, MORALS AND WELFARE
TITLE 9 VEHICLES, TRAFFIC AND RAIL TRANSPORTATION
TITLE 10 STREETS, PUBLIC WAYS, PARKS, AIRPORTS AND HARBORS
TITLE 11 UTILITIES AND ENVIRONMENTAL PROTECTION
TITLE 12 RESERVED
TITLE 13 BUILDINGS AND CONSTRUCTION
TITLE 14 RESERVED*
TITLE 14A ADMINISTRATIVE PROVISIONS OF THE CHICAGO CONSTRUCTION CODES*
TITLE 14B BUILDING CODE*
TITLE 14C CONVEYANCE DEVICE CODE*
TITLE 14E ELECTRICAL CODE*
TITLE 14F FIRE PREVENTION CODE*
TITLE 14G FUEL GAS CODE*
TITLE 14M MECHANICAL CODE*
TITLE 14N 2022 ENERGY TRANSFORMATION CODE*
TITLE 14P PLUMBING CODE*
TITLE 14R BUILDING REHABILITATION CODE*
TITLE 14X MINIMUM REQUIREMENTS FOR EXISTING BUILDINGS*
TITLE 15 FIRE PREVENTION
TITLE 16 LAND USE
TITLE 17 CHICAGO ZONING ORDINANCE
TITLE 18 BUILDING INFRASTRUCTURE
APPENDIX TO THE MUNICIPAL CODE OF CHICAGO (RESERVED)*
TABLES
Chicago Zoning Ordinance and Land Use Ordinance
Loading...
14X-5-505.2 General means of egress.
Means of egress must meet the requirements of this section.
14X-5-505.2.1 Ceiling height.
Means of egress must have a ceiling height of not less than 7 feet (2.1 m) from the floor, with no projection below 6 feet 8 inches (2033 mm) from the floor.
Exception: Within dwelling units a ceiling height of not less than 6 feet 8 inches (2033 mm) from the floor is allowed.
14X-5-505.2.2 Width.
The required width or capacity of the means of egress may not be reduced along the path of egress travel until arrival at the public way.
14X-5-505.2.3 Elevators, escalators and moving walks.
Elevators, escalators, and moving walks may not be used as a component of a required means of egress.
Exception: Existing escalators and moving walks in existing buildings.
14X-5-505.3 Occupant load.
Occupant load in existing buildings must be determined in accordance with Section 1004 of the Chicago Building Code.
14X-5-505.4 Means of egress capacity.
The capacity of the means of egress and means of egress components must be determined in accordance with Section 1005 of the Chicago Building Code. A building may not be occupied in a manner that will exceed its calculated egress capacity.
14X-5-505.4.1 Posted occupant capacity.
Where the occupant capacity of a building is posted or required to be posted, it is unlawful to cause or allow the building to be occupied in a manner that will exceed the posted occupant capacity.
14X-5-505.5 Number of exits and exit access doorways.
Every occupiable space within an existing building must be provided with not less than the minimum number of exits or exit access doorways required by Section 1006 of the Chicago Building Code. For purposes of this requirement, permitted fire escapes complying with Section 14X-5-505.12 are recognized as exits.