14X-5-505.1.2.2 Operation of doors and gates.
Means of egress doors and gates must be readily openable from the side from which egress is to be made without the need for a key, special knowledge, or effort.
Exception: Doors and gates may be locked with hardware of a type allowed by the Chicago Building Code where such hardware is in working condition.
(Amend Coun. J. 2-19-20, p. 14473, Art. V, § 27)
14X-5-505.2 General means of egress.
Means of egress must meet the requirements of this section.
14X-5-505.2.1 Ceiling height.
Means of egress must have a ceiling height of not less than 7 feet (2.1 m) from the floor, with no projection below 6 feet 8 inches (2033 mm) from the floor.
Exception: Within dwelling units a ceiling height of not less than 6 feet 8 inches (2033 mm) from the floor is allowed.