18-29-710.3  Underground drainage piping.
   Any portion of the drainage system installed underground or below a basement or cellar shall not be less than 4 inches (100 mm) in diameter.
Table 18-29-710A
Building Drains and Sewers
Diameter of Pipe (inches)
Maximum Number of Drainage Fixture Units Connected to any Portion of the Building Drain or the Building Sewer, Including Branches of the Building Draina
Slope per Foot
1/6 inch
1/8 inch
1/4 inch
1/2 inch
Diameter of Pipe (inches)
Maximum Number of Drainage Fixture Units Connected to any Portion of the Building Drain or the Building Sewer, Including Branches of the Building Draina
Slope per Foot
1/6 inch
1/8 inch
1/4 inch
1/2 inch
1 1/4
1
1
1 1/2
3
3
2
21
26
2 1/2
24
31
3
36
42
50
4
180
216
250
5
390
480
575
6
700
840
1,000
8
1,400
1,600
1,920
2,300
10
2,500
2,900
3,500
4,200
12
2,900
4,600
5,600
6,700
15
7,000
8,300
10,000
12,000
 
For SI: 1 inch = 25.4 mm, 1 inch per foot = 0.0833 mm/m.
a The minimum size of any building drain serving a water closet shall be 3 inches.
Table 18-29-710B
Horizontal Fixture Branches and Stacks a
Diameter of Pipe (inches)
Any Horizontal Fixture Branch
Maximum Number of Fixture Units that may be Connected to:
One Stack of 3 Stories in Height or 3 Intervals
More than 3 Stories in Height
Total for Stack
Total at One Story or Branch Interval
Diameter of Pipe (inches)
Any Horizontal Fixture Branch
Maximum Number of Fixture Units that may be Connected to:
One Stack of 3 Stories in Height or 3 Intervals
More than 3 Stories in Height
Total for Stack
Total at One Story or Branch Interval
1 1/2
3
4
8
2
2
6
10
24
6
2 1/2
12
20
42
9
3
20
30
60
16
4
160
240
500
90
5
360
540
1,100
200
6
620
960
1,900
350
8
1,400
2,200
3,600
600
10
2,500
3,800
5,600
1,000
12
3,900
6,000
8,400
1,500
15
7,000
 
For SI: 1 inch = 25.4 mm.
a Does not include branches of house drain.