18-29-709.5  Values for indirect waste receptor.
   The drainage fixture unit load of an indirect waste receptor receiving the discharge of indirectly connected fixtures shall be the sum of the drainage fixture unit values of the fixtures that discharge to the receptor. If this drainage fixture value is less than the indirect waste receptor drainage fixture value given in Table 18-29-709.1 or Table 18-29-709.2, then the values in the referenced tables shall be used.