All joint surfaces shall be cleaned. An approved flux shall be applied where required. The joint shall be brazed with a filler metal conforming to AWS A5.8.
18-29-705.4.2 Mechanical joints.
Mechanical joints shall be installed in accordance with the manufacturer's instructions.
18-29-705.4.3 Threaded joints.
Threads shall conform to ASME B 120.1. Pipe joint compound or tape shall be applied on the male threads only.
18-29-705.4.4 Welded joints.
All joint surfaces shall be cleaned. The joint shall be welded with an approved filler metal.