You are viewing an archived code
Sprinkler piping in small unheated areas exposed to frost shall be filled with pure glycerine solution only. The total number of sprinklers in such areas shall not exceed 20. A durable sign or metal tag shall be firmly attached to the solution filling connection plainly marked “THE CITY CODE REQUIRES THE USE OF A PURE GLYCERINE SOLUTION ONLY”.
The sprinklers on the piping filled with glycerine shall be below the interface between the water and antifreeze solutions provided that sprinklers may be located above the interface between the water and the antifreeze when a check value with a one-thirty-second inch hole in the clapper is provided in a U-loop. A water control valve and two small solution test valves shall be provided.
(Prior code § 91-33; Amend Coun. J. 10-30-96, p. 31216, § 1)