15-16-311  Test manifold.
   Each fire pump which supplies an automatic sprinkler system shall be provided with a discharge test manifold having one two and one-half inch corrosion resistant valve for each 250 gallons per minute of rated pumping capacity; however, no more than six valves need be provided. The discharge test manifold shall be located on an outside wall in a location which will permit safe discharge and drainage of water.
(Added Coun. J. 10-30-96, p. 31216, § 1)