Skip to code content (skip section selection)
Compare to:

You are viewing an archived code

15-16-310  Fire pumps.
   Fire pumps and auxiliary equipment, including controllers required to form complete pumping units, shall be of a type designed and developed for sprinkler service. The installation shall comply with NFPA 20-2013. The suction pipe shall be six inches for 500 and 750 gallons per minute pumps and eight inches for 1,000 and 1,500 gallons per minute pumps. The city connection shall be increased two inches if used for both domestic consumption and fire protection demands when the domestic service exceeds two inches.
   In each case the pump used shall be selected to meet the conditions surrounding the installation. The pumping unit shall be designed to develop full capacity at its rated pressure. The design and installation of a pump shall be such that under any flow rate the intake pressure at the pump shall be not less than five pounds per square inch.
   A fire pump shall be automatic in operation. A time delay device set for one minute for each ten horsepower of motor rating but not to exceed seven minutes shall be provided. A separate automatically controlled centrifugal pressure maintenance pump to avoid too frequent starting and stopping of the fire pump shall be provided.
(Prior code § 91-15; Amend Coun. J. 10-30-96, p. 31216, § 1; Amend Coun. J. 9-6-17, p. 55278, Art. VII, § 23)